BIDDER'S INQUIRIES & RESPONSES
DISTRICT 11 CONSTRUCTION

THE MANDATORY PREBID MEETING FOR CONTRACT 11-080104 WILL BE ON FRIDAY, SEPTEMBER 25, 2009 AT THE FOLLOWING LOCATION: 4050 TAYLOR STREET, SAN DIEGO, CA 92110

THE MEETING WILL BE HELD IN BUILDING 1, FLOOR 1, GARCIA ROOM, FROM 1:30 P.M. TO 4:30 P.M.

PLEASE CALL (619) 688-6635 WITH QUESTIONS.



CONTRACT NO: 11-080104
ROUTE / KP 11-SD-76-R11.7/21.1
LOCATION In San Diego County In And Near Oceanside From 0.8 Km West Of Melrose Drive To 1.0 Km East Of South Mission Road
DESCRIPTION Construct A 4-lane Highway.
ESTIMATE $80,000,000
WORKING DAYS

900

ADVERTISE DATE 09/08/2009
BID OPENING 10/29/2009
FINAL POSTING
10/28/09  @ 15:00


The Caltrans District 11 Office is located at 4050 Taylor Street, San Diego, CA 92110. The District 11 Duty Senior telephone number is (619) 688-6635. Please submit all inquiries in the proper format by fax to (619) 688-6988 or e-mail to:
Duty_Senior_Const_District11@dot.ca.gov.
The responses to bidder' inquiries, unless incorporated into a formal addenda to the contract, are not a part of the contract and are provided for the bidder's convenience only. In some instances, the question and answer may represent a summary of the matters discussed rather than a word-for-word recitation. The responses may be considered along with all other information furnished to prospective bidders for the purpose of bidding on the project. The availability or use of information provided in the responses to bidder' inquiries is not to be construed in any way as a waiver of the provisions of Section 2-1.03 of the Standard Specifications or any other provision of the contract, the plans, Standard Specifications or Special Provisions, nor to excuse the contractor from full compliance with those contract requirements. Bidders are cautioned that subsequent responses or contract addenda may affect or vary a response previously given.
Caltrans District 11 Construction Department has developed this method of answering Bidder's Inquiries to better serve the needs of the Contractors who bid on our Projects. Caltrans District 11 Construction Department will post all of the questions submitted by any of the contractors that are registered Planholders for that Contract, but reserves the right to not answer any questions deemed unsatisfactory for public viewing.
The BIDDER'S INQUIRIES & RESPONSES will be updated continuously and all attempts will be made to do the final posting by 15:00 on Wednesday prior to the bid opening.
INFORMATION AVAILABLE


INFORMATION HANDOUT
9/14/09

BID ITEMS
 SPECIALS
PLANS
 PLANHOLDERS
INFORMATION HANDOUT**
provided in Addendum No. 1 on 10/20/09
X-SECTIONS
10/06/09
 MANDATORY PRE-BID
MEETING INFO


 
LOG OF BORINGS
for existing
Br. No. 57-0957




** NOTE:
The INFORMATION HANDOUT provided in Addendum No. 1 includes all the SUPPLEMENTAL PROJECT INFORMATION (as Advertised and new documents in Addendum No.1) per Section 5-1.08.

ORDERING PROJECT PLANS AND SPECIFICATIONS

Cost per set: Bidders: $139, Non-bidders: $132, 10% UDBE Requirement

                                                                                        ADDENDA


ADDENDUM NO. 1
 
Issued 10/20/2009
ADDENDUM NO. 2
  Issued 10/27/2009

 

BIDDER'S INQUIRY SUBMITTAL FORM


Inquiry No.
Inquiry

1

  Q:09/15/09
R:10/20/09

Plan Sheet / Specification Reference= 120, Minor Concrete (Minor Structure), Sheet 416

Question= Drainage System 28, Unit B & D, call out Box Culvert Wingwalls.  The quantity shown for these Wingwalls is 1550 M3 and is reflected on the Bid Item List under Minor Concrete (Minor Structure).  This quantity seems to be a bit excessive.  Please confirm that this is the correct quantity or update the Bid Item List to reflect the correct quantity.

  • See Addendum No. 1

2

  Q:09/15/09
R:09/21/09



R:10/13/09

Plan Sheet / Specification Reference=  Core samples.

Question=   Logs of Test Borings and Please provide contact information for the Transportation Laboratory to view core samples.

  • For logs of test borings, please see page 28 of the advertised special provisions right below the "Cross Sections" in the table.
  • For contact info, please look in the amended Standard Specifications that are in the back of the "Special Provisions", (page 8 of 217) Section 2-1.03B, "Supplemental Project Information".
  • The LOGS OF TEST BORINGS for the project are included in the contract plans.
    Contact information for the COREROOM is per the AMENDMENTS TO THE STANDARD SPECIFICATIONS DATED JULY 1999 included in the Contract Documents on amendments page "8 of  217":
            2-1.03B Supplemental Project Information
            If rock cores are available, you may view them by sending a request to Coreroom@dot.ca.gov
            Make your request at least 7 days before viewing. Include in your request:
            1.    District-County-Route
            2.    Bridge number
            3.   Contract number
            4.   Viewing date
            5.   Contact information, including telephone number. 

3

  Q:09/17/09
R:09/21/09
Plan Sheet / Specification Reference=

Question= I was wondering if I could possibly find out if this project is receiving ARRA funds.  Is there a link or particular page where ARRA funded/aided projects are listed?

  • Yes, this project has ARRA funds.

4

  Q:09/17/09
R:09/21/09
Plan Sheet / Specification Reference=

Question= I did not see archaeological services listed for this project, will 
that be advertised somewhere else?

  • No, per Section 5-1.16 ARCHAEOLOGICAL AND NATIVE AMERICAN RESOURCES, the Archeologist and Native American Representative will be provided by the State for this project.

5

  Q:09/25/09
R 1:09/28/09
R 2:09/29/09
R 3: 10/20/09
Plan Sheet / Specification Reference=  Bid Items 109, 110, 111 - Permanent Steel Casing.  Special Provisions page 210, "Permanent Steel Casing Installation".

Question= Will casing installation by vibratory hammer or oscillator be allowed in addition to the methods listed in the Special Provisions?
  • Please bid per the current contract documents
  • The above answer might be revised. Please check back at a later time.
  • See Addendum No. 1

6

  Q:09/29/09
R:09/30/09
R:10/12/09
Plan Sheet / Specification Reference= Specials Page 70 List of Parcels Plan Sheet 26 (K-2)

Question= No access dates have been provided for Parcels
33135,33136,33137. Please provide date when access will be provided.

  • The State of California owns all three parcels in question and the areas cross hatched on Sheet K2 are available at initial bid. The property owned by the State that is beyond the limits of the cross hatched areas on parcel 33135 is also available for contractors use. Partial use of 33136 and 33137 may also be possible but is subject to environmental restrictions and would need to be arranged with the Resident Engineer.
  • For site specific availability of PARCELS 33135, 33136 and 33137, Please click here  SITE PLAN  for limits available to the Contractor. The Contractor may propose staging use by submitting a request with SWPPP staging area plans to the Resident Engineer.

7

  Q:09/29/09
R:10/07/09
Plan Sheet / Specification Reference= Plan Sheet 40 (L-12)

Question= There are no Sections included in the plans for RW1 shown on
Sheet L-12. Are cross sections available for that Retaining Wall.


8

  Q:09/29/09
R:09/30/09
Plan Sheet / Specification Reference= Special Provisions page 68 Section 10-1.01

Question= The referenced section prohibits pile driving between 2-15 and
9-15. Does this apply to drilling and pouring CIDH piling?

  • No, only pile driving is prohibited during the bird nesting season February 15 through September 15 at Br. No. 57-1208R.

9

  Q:09/29/09
R:10/20/09
Plan Sheet / Specification Reference= Special Provisions page 147 Section 10-1.35

Question= The referenced section indicates a price of $ 11,795 good thru
7-30-2009. Should that number be considered an allowance or will
Caltrans provide a new price?
  • See Addendum No. 1.

10

  Q:09/29/09
R:10/01/09
Plan Sheet / Specification Reference= Special Provisions page 156 Section 10-1.39

Question= The referenced section indicates the possibility of stepped
slopes.Portions of the job may require drill and shoot. Will stepped
slopes be required in these areas?
  • No, areas that will be excavated in accordance with Section 10-1.41 ROCK EXCAVATION (CONTROLLED BLASTING) do not require stepped slopes. Stepped slopes shall be required as defined in Section 10-1.39 EARTHWORK and as shown on Construction Details sheet C-24 (133 of 1204).

11

  Q:09/29/09

R1: 10/22/09

Update to R1
R2: 10/27/09

Plan Sheet / Specification Reference= Plan Sheets 454 thru 456

Question=

1)The sheets do not indicate any profiles or have invert
elevations. Please provide the invert elevations at the tie ins or
provide copies of the As Built information.

  • See Addendum No. 1


2) There is no Bid Item for 250 MM PVC sewer pipe relocation or 150 MM
DI sewer. Furthermore the limits of the 150MM reloaction are not clear.

  • See Addendum No. 1


3)At the prebid it was indicated that there would no opening cutting of
Highway 76 for the installation of the sewer crossing at Sta 138 +/- 70.
Is this correct? If so what size casing will be required and where is
the bore and casing to be paid.

  • See Addendum No. 1


4) There also is no shutdown information or flows for bypass pumping
provided. The sewer district should have this information please provide
this to the bidders so that all the bidders do not have to call the
districts.

  • Submitted for Consideration.
  • City of Oceanside requirements for shutdown:
  • an 8" bypass
  • 7 days advance notice for shutdowns
  • No Shutdowns on Mondays or Fridays (only Tues/Wed/Thurs)
  • the material for the tie-in needs to be on site and reviewed/approved by their City Inspector

  • Rainbow Municipal Water District requirements for shutdown:
  • 3 weeks notification
  • Not on Mondays
  • 8am to 4pm (normal hours)


12

  Q:09/29/09
R:10/22/09

Plan Sheet / Specification Reference= Utility Relocation by others pages 35 thru 38

Question= The Specials indicate SDG&E OH & UG will be given different
time allocations depending on which sequence they are working. It also
indicates they will have exlusive use of the relocation area. Are they
willing to commit multiple crews and does this exclusivity apply to OH &
UG crews. Based on the Staged Construction this does not necessarily
make sense. Please clarify.

  • Please follow the work window provided.


13

  Q:09/29/09
R:10/15/09
Plan Sheet / Specification Reference= Utility Relocation by others pages
35 thru 38. Plan sheets U-4 thru U-8

Question= The Specials indicate SDG&E Gas will be relocating a gas line.
Will fill be allowed to be placed over the top of the existing line
prior to that relocation and can the line be abandoned in place?

  • The existing 6" diameter gasline from 137+50 to 151+30 may be filled overand left in operation for the duration of Stage 4. (per prior concurrence with SDG&E)

14

  Q:09/29/09
R:10/20/09
Plan Sheet / Specification Reference= Plan sheets U-39 thru U-40

Question= The Specials and plans indicate that the existing AC water line is to be removed or abandoned.
Both,
  • See Addendum No. 1
If the line is removed will Caltrans sign the manifest as Generator?
  • The City of Ocenaside is the Generator, they will sign the manifest.
How will the disposal of hazardous waste be paid?
  • See Addendum No. 1

15

  Q:09/29/09
R:10/01/09
Plan Sheet / Specification Reference= Plan Sheets U-4 thru U-48

Question=

1)Have Caltrans and the Utilities completed and executed all
the Joint Use Agreements (JUA's), Consent to Common Use Agreements
(CCUA's), Easements or any and all Encroachment Permits required to
relocate these utilities? Based on the Bid Documents it would appear
that all these agreements have been executed by both parties. Please
confirm.

  • JUAs and CCUAs are executed after relocation of the facilities. 
  • No new easements are required for this project since all utilities will be within the Right of Wayfor the new highway facility.
  • Encroachment Permits are being processed to meet the construction schedule. 
2) Have all the fees been paid?
  • State mandatory utility relocation is exempt from Encroachment Permit fees.
3) Are any of these utility ROW's be acquired by Emminent Domain? If so
when will the contractors have access?
  • Yes.  some of the R/W is being acquired by Eminent Domain
  • As defined in the Contract Special Provisions Section 10-1.01 ORDER OF WORK, if there are any updates they will be provided by addenda.

16

  Q:09/29/09
R:10/13/09
Plan Sheet / Specification Reference= Prebid Meeting

Question= At the Pre Bid meeting Caltrans indicated that a limited NTP
would be granted for mowing and clearing prior to all the necessary
submittals and schedules being approved so that clearing and mowing
could be completed prior to 2-15. Please confirm.

  • Yes, a limited Notice to Proceed (NTP) will be granted to CHAIN AND MOW provided the following information is submitted and few conditional changes pending.
1) The CPM Schedule for the Initial Bid Package (IBP) must be submitted and conditionally approved.
2) The SWPPP Submittal for the IBP plans must be submitted and conditionally approved.
3) A SWPPP Submittal is not required for CHAIN AND MOW of the IBP area but a commitment to place BMPs as necessary during the operation based on the current field conditions at the time will be required.
4) A SWPPP Submittal is not required for CHAIN AND MOW of the Sequence 1 and 2 area but a commitment to place  BMPs as necessary during the operation based on the current field conditions at the time will be required.
5) ESA fencing placed prior to CHAIN AND MOW of Sequence 2 as necessary.

17

  Q:09/29/09
R:10/14/09
Plan Sheet / Specification Reference= Specials page 106 Section 10-1.16

Question= Temporary Water Diversion section requires the contractor to
submit a Hydraulic Analysis for the San Luis Rey River prior to any
diversion work. Does this analysis need to include the 562 sq miles
alluded to at the pre bid or just sufficient for the contractors work.

  • The exact quote was from Section 5-1.08 SUPPLEMENTAL PROJECT INFORMATION: Item U. Missive for Thalweg, dated July 1, 2009. "The San Luis Rey River extends over 55 miles across northern San Diego County forming a watershed with an area of approximately 562 square miles." Yes, the watershed/ defined drainage basin area should be addressed in the Analysis. The flow rates provided in the Missive should also be used to understand how the work area could be impacted by historical flow patterns when preparing the Analysis.

18

  Q:09/29/09

R:10/22/09

R:10/23/09

Plan Sheet / Specification Reference= Plan Sheets U-35 to U-48 Water Line Relocations

Question=

1. No shutdown information was provided for bidding purposes.
The water districts should be able to provide that information to
Caltrans rather than have all the bidders contact them.

    • Submitted for Consideration.
    • 7 days advance notice for shutdowns
    • No Shutdowns on Mondays or Fridays (only Tues/Wed/Thurs)
    • The material for the tie-in needs to be on site and reviewed/approved by their City Inspector

2. WTR-6 does not show the existing storm drainage. Does that storm
drain system affect this relocation as designed?

  • Yes, needs to be staged after traffic moves to the new Ostrich Farm Creek Bridge.

3. What Item is the Temporary Highline on Sheet 35 to be paid under?

    • Submitted for Consideration.
    • Your attention is directed to tha last paragraph of Section 10-4.59B WATER LINE PAYMENT

4. Bid Item 174 as stated does not match the Q heets or plans. Please
clarify

  • Q Sheets and Bid Item are correct.

19

  Q:09/29/09
R:10/15/09
Plan Sheet / Specification Reference= Plan Sheets U-4 to U-5 Gas Line Relocation

Question= Does the 75 MM Gas Line get relocated or is it abandoned?

  • SDG&E must remove at least the portion from 138+70 to 139+20  at the end of Stage 4 and from 139+20 to 140+80 during Stage 6. For a total of 210 m (700 ft)

20

  Q:09/29/09
R:10/05/09
Plan Sheet / Specification Reference=

Question= "Federal conformity regulations require analysis of construction impacts when construction activities would last for more than 5 years. The proposed project would last less than 5 years; therefore, no quantitative estimates of regional construction emissions have been made." (Final Environmental Impact Report/ Environmental Impact Statement State Route 76 Melrose to South Mission San Diego County, 3-183, 2008). Are the impacts associated with operating an asphalt or a concrete plant within the right-of-way included in the exclusion for analysis of construction impacts for projects of less than 5 year duration?
  • Per 40 CFR 93.123, analyses are not required to consider construction-related activities which cause temporary increases in emissions.  Temporary increases are those which occur only during the construction phase and last five years or less at any individual site.
May a contractor set up and operate an asphalt or concrete plant within the right-of-way without further analysis of potential impacts?

  • Yes, since the temporary impacts are excluded. Site specific location requests shall be in conformance with the requirements of the contract plans and specifications, attention is directed to the provisions in Section 7-1.01 "Laws to be Observed", of the Standard Specifications. 

21

  Q:09/29/09
R:10/20/09
Plan Sheet / Specification Reference=  Section 2 Bidding

Question= The Special Notices state: “The Department is implementing new Disadvantaged Business Enterprise requirements for Underutilized Disadvantaged Business Enterprises (UDBE). Section 2, "Bidding," under subsection titled "Disadvantaged Business Enterprises" and Section 5, "General," under subsection titled "Performance of UDBEs" of these special provisions cover the UDBE requirements.” In Section 2 “bidding” there is not a subsection titled “Underutilized Disadvantaged Business Enterprises”; In Section 5 “General” under subsection titled “Performance of UDBEs” It states: “UDBEs must perform work or supply materials as listed in the Caltrans Bidder - UDBE - Commitment form specified under Section 2, "Bidding," of these special provisions.” Section 2 Bidding contains no information regarding the Caltrans Bidder – UDBE – Commitment Form.  In the Bid book the Caltrans Bidder – UDBE – Commitment states: “This information may be submitted with your bid proposal.  If it is not, and you are the apparent low bidder or the second or third low bidder, it must be submitted and received as specified in Section 2 of the Special Provisions.”  Again, these requirements are not addressed in Section 2.  Please provide Section 2 Bidding requirements for UDBE.
  • See Addendum No. 1

22

  Q:09/29/09
R:10/05/09
Plan Sheet / Specification Reference= 

Question= The Director and County Counsel for the San Diego Air Pollution Control District (APCD) interpret the regulations for the use of portable equipment (crushers, screens, asphalt, and concrete batch plants) registered under the statewide PERP program as an absolute 12 month limitation for their use on any site ("Any engine or equipment unit such as back-up or stand-by engines or equipment units, that replace engine(s) or equipment unit(s) at a location, and is intended to perform the same or similar function as the engine(s) or equipment unit(s) being replaced, will be included in calculating the consecutive time period. In that case, the cumulative time of all engine(s) or equipment unit(s), including the time between the removal of the original engine(s) or equipment unit(s) and installation of the replacement engine(s) or equipment unit(s), will be counted toward the consecutive time period", Regulation to Establish a Statewide Portable Equipment Registration Program, Section 2452(cc)(1), 2007). APCD has determined that the 12 month time limit begins the day the equipment arrives at the site and terminates 12 months later. APCD does not recognize the legitimate removal of portable equipment from the site (not for the purpose of circumventing the rules, id at Section 2452(cc)(3)) as the end of a consecutive 12 month period (The engine or equipment unit is not portable if...the equipment will reside at the same location for more than 12 consecutive months..., id at Section 2452(cc)(1)). Projects that last more than 12 months are considered a Stationary Source. Stationary sources require an Authority to Construct with a Permit to Operate (Air pollution Control District County of San Diego, Regulation II, Rule 10 and Rule 12, 2007). Furthermore, APCD has determined that the entire project would be considered as a stationary source because the construction project takes place on one or more contiguous properties under common ownership (id at Rule 12 20.1(c)(67), "Stationary Source means an emission unit...located on the same or contiguous properties and which units are under common ownership or entitlement to use").  Will a variance for the use of portable equipment, for more than 12 months, be made available to the contractor or will the contractors have to apply for a Permit to Operate if their equipment is on the project for more than 12 months?

  • No, the State cannot apply for a variance for the contractors equipment. Contractors may apply for a variance based on their equipment and proposed length of use.

23

  Q:09/30/09
R:10/27/09
Plan Sheet / Specification Reference= 

Question= Under section 5-1.22 Non-highway Facilities (Utilities) of the Special Provisions, a RELOCATION schedule is listed showing Notification/Working days for each utility in each Sequence (page 35).  Pages 36-38 show specific RELOCATION/INSTALLATION activities the utilities will perform, but there is no schedule of notification days required, or the number of working days required to complete these tasks. Please indicate what Notification/Working Days are required for the activities on pages 36-38.

  • City of Oceanside requirements for shutdown:
  • an 8" bypass
  • 7 days advance notice for shutdowns
  • No Shutdowns on Mondays or Fridays (only Tues/Wed/Thurs)
  • the material for the tie-in needs to be on site and reviewed/approved by their City Inspector

  • Rainbow Municipal Water District requirements for shutdown:
  • 3 weeks notification
  • Not on Mondays
  • 8am to 4pm (normal hours)

24

  Q:09/30/09
R:10/22/09

Plan Sheet / Specification Reference=  Bid Item 174 - 200 mm Steel Cement Mortar Lined and Coated Water Main (Class-350)

Question= On Sheet UQ-3, Page 520, under the heading"200 mm Steel CML&C Water Main (Class-350)" it directs me to Sheet U-41 between Sta. 174+10.00 and 174+90.00, with a quantity of 142.00 m. Between those stations I find 300 mm CMI&C.
Could you please clarify the size of CMI&C between Sta. 174+10.00 and 174+90.00 on Sheet U-41?
If in fact between
Sta. 174+10.00 and 174+90.00 on Sheet U-41 is 300 mm CMI&C where is the pipe that gets paid in bid Item 174?

  • See Addendum No. 1

25

  Q:09/30/09
R:10/22/09

Plan Sheet / Specification Reference=  On sheet 496, Plan U-36, Approximate station 41+20.00, it appears that there is a waterline that connects to “WTR1” and crosses the proposed SD-76.  This waterline has no call outs or construction notes.

Question= Is this part of the work for this contract?

  • See Addendum No. 1

26

  Q:10/05/09
R:10/05/09
Plan Sheet / Specification Reference=

Question= Can the State release a list of prime contractors that attended the mandatory Pre-Bid?

  • Yes.  The list of all attendees of the Pre-Bid Meeting is now available on this website. Please click the link below: 
  • MANDATORY PRE-BID_MEETING INFO

27

  Q:10/06/09
R:10/20/09

Plan Sheet / Specification Reference=

Question= It is stated in the Notice to Bidders that there is a UDBE contract GOAL of 10 percent. However, in the list of advertised projects out to bid on the CALTRANS website and in the Bidder's Inquiry site for District 11, a UDBE REQUIREMENT of 10 percent is stated.
Please confirm that the 10% UDBE participation is a goal, as is stated in the special provisions, and not a requirement?

See Addendum No. 1

Yes, it is a goal. The goal is a requirement per Section 2-1.03 "Disadvantaged Business Enterprises":  
"Meet the UDBE goal shown in the Notice to Bidders or demonstrate that you made adequate good faith efforts to meet this goal."


28

  Q:10/07/09
R:10/13/09
Plan Sheet / Specification Reference= Item# 73 Erosion Control Type D Seed Mix

Question= We are seed suppliers of Native seed in California. I am trying to give prices and seed availability to my customers, who sub-contract the erosion control for this project.
This question pertains to page 166-167. The plans indicate 47 hectares for erosion control type D seed mix, but the pages list 3 different seed mixes under that category. (Seed Type 1, 2, & 3) I need to know the area size for each of these seed mixes so I may determine the amount of seed that would be needed for each mix.
You may either let me know in total Kgs per mix or total hectares per mix.
  • See PLAN SHEET LANDSCAPE DETAILS LD -2 (sheet 961 of 1204).

29

  Q:10/07/09
R:10/15/09
Plan Sheet / Specification Reference= Item 148, Sheet 325, Drainage Profile for Drainage Plan 26B

Question= Is there a drainage profile for drainage system 26B? The layout drawings do not provide enough information.

  • DS 26B is within Sequence 2, the DRAINAGE PROFILE shall be provided per Section 1 of the Special Provisions 70 days after delivery of Sequence 1. The drainage system is shown on the DRAINAGE LAYOUT D-8 (sheet 281 of 1204). This is still under design review and study and it will be updated once design is completed.

30

  Q:10/09/09
R:10/14/09
Plan Sheet / Specification Reference= Sanitary Sewer SSD-1

Question= Are these Manholes to be T-Lok or plain as indicated?
  • No, they are as indicated on SSD-1 (sheet 457 of 1204) and defined in the Special Provisions.

31

  Q:10/09/09
R:10/13/09
Plan Sheet / Specification Reference= Storm Drain System 3 DP-2A

 
Question= Indicates work by others, who & when?
  • The work (by others) will be done under an encroachment permit issued to the Vista Unified School District.
  • This work is scheduled to be complete prior to the SR 76 contractor receiving completed Sequence #2 plans

32

  Q:10/09/09
R:10/15/09
Plan Sheet / Specification Reference= Storm Drain Issues. Please clarify and revise accordingly

Question=
    1. System 70 a & b plan & profile do not match the quantity sheet.
  • System 70 A and B within Sequence 1 were still under study during time of submittal. This system will be revised once the study and design is completed
2. System 96 has two O designations on the plan sheet. Is the O that crosses Hwy 76 suppose to be the ad removal. If so it would appear this could be abandoned rather than removed is that possible?
  • The existing system that crosses 76 is part of system 96 within Sequence 3.  This system is still under study and updated information will be provided once design is complete.
3. System 97 shown on D-27 and DP-57 do not completely match. DP-57 has no profile information. Please provide.
  • system 97 within Sequence 3 is still under design review and study and it will be updated once design is completed
4. System 102 DP-61 (f) appears to be an in correct size.
  • System 102 is within Sequence 3.  Element f is tentatively being proposed to be revised to be a 25.74m of 600 mm RCP. The final details will be made more clear with the release of the sequence 3 plans
5. System 110 plan sheet D-31 & 32 do not completely match the profile sheet DP-66. Plan sizes are called out that are not on the Q Sheets or Bid Schedules as well as structures are shown and not called out.
Please revise the quantities for this system.
  • System 110 within Sequence 3 is still under design. An update of this system will be provided once the design is completed.
6. System 116 DP- 70 indicates the material under the existing pipe is to be removed and recompacted. Is this correct?
  • This is correct, the soils are unsuitable (duff) per Geotech recommendations and it will be required to be removed and recompacted, approximate limits shown on profiles.
7. System 30 DP-19 calls for 1500 mm RCP. There is no bid item for that pipe size.
  • System 30 is indeed a 1500mm pipe and has been incorrectly identified and shown on the quantity sheets as 1200mm pipe. The quantities were not updated prior to submittal and the quantity revision will be made as part of a subsequent sequence.
8.There seems to be a significant difference between the culvert removal called out,the Bid Sheet, the plan sheets, the profile sheets and the Q sheets.
  •  All plans/quantities will be verified prior to the release of future sequences as that design finalizes.  Systems in the IBP should be accurate and other systems outside of IBP may vary.
9. The Q Sheets for 1200 MM pipe do not necessarily match the plan call outs please clarify.
  • Please be more specific to which systems that you are referring to.  It was noted in questions 7 above that the quantities for the 1500mm pipe for system 30 were quantified as 1200 mm pipe.  This will be updated on future submittals.
10. It appears Bid Item 160 Q sheet does not match the plans for System 51.
  • System 51 is an existing system that requires that the 450 mm pipe be removed only.  There is no new pipe installation and the figure on sheet DQ26 showing 13 M of 450 MM CSP is incorrect.
11.Some of the 600 MM pipe is shown on the plan sheets as CSP while the Q sheets call it out as APC which is correct. The Bid sheet will be affected.
  • The Q sheet is the signed sheet and is correct.

12. Bid Item 169 does not appear to be a correct quantity.

  • Bid Item 169 is 900 mm RCP Riser.  This quantity will be updated on future submittals.

33

  Q:10/09/09
R:10/15/09
Plan Sheet / Specification Reference= Bid Item # 48, Plan Sheet 869

 
Question= Bid Item # 48 Cold Plane Asphalt Concrete Pavement has a quantity of 24,100 M2, Plan Sheet 869 provides a summary with the locations for the Cold Plane Work. Can you please provide the Cold Plane limits from station 181+60 to 193+00, and also from 203+50 to 207+00. The Layout Sheets don’t show the Cold Plane limits matching the quantities shown on sheet 869 for the mentioned stationing.
  • On sheet No. L-20, L-21, L-22, L-23, L-24, L-29, and L30 there are portions of the existing highway that will remain in place. The cold plane and overlay areas are actually referring to proposed work on existing SR76 that will remain in place. The cold plane areas are not shown on the plan sheets and will be added as part of a subsequent sequence. However, the quantities are listed for anticipated resurfacing work on the existing roadway before it's turned over to the County.

34

  Q:10/09/09
R:10/12/09
Plan Sheet / Specification Reference= Cross Sections

Question= Regarding cross sections posted 10/6/09, were there any changes made to previoulsy posted sections? If so, what stations were changed?
  • No other changes were made, only the cross sections for "RW-1" along the "ORR" LINE were added

35

  Q:10/12/09
R:10/13/09
Plan Sheet / Specification Reference=  On sheet No.2 under the 'Typical Structural Sections' No.7

 
Question= On sheet No.2 under the 'Typical Structural Sections' No.7 indicates a variable HMA overlay and ( 0.05-0.45).  Is this to be interpreted as mm or is this in feet?
  • The dimensions shown are mistakenly shown in Meters not MM as listed on the page.

36

  Q:10/13/09
R:10/14/09

R:10/15/09

The 10/15/09
Reply was
updated on
R:10/26/09



The 10/26/09
Reply was
updated on
R:10/27/09



Plan Sheet / Specification Reference= Foundation Report Memorandum for Bridge #57-1208R (12/11/08)

 
Question= Page 10 of the issued Foundation Report Memorandum for Br. #57-1208R dated December 11, 2008 states that the rock cores and rock strength test data are available for viewing.  We are schedule to view both on 10-15-09.

  • Here are the Geotechnical Laboratory Rock Strength Test Data and Point Load Test documents available for BR. # 57-1208R: Click Here for Test Data
Additional test data documents available for BR. No. 57-1208. Please click the links below: Added by Addendum No. 1  to Section 5-1.08
Y.    Geotechnical Laboratory Rock Strength Test Data Br. No. 57-1208R GL08-017, dated April 15, 2008
Z.     Geotechnical Laboratory Rock Strength Test Data Br. No. 57-1208R GL08-038, dated May 13, 2008
AA.  Geotechnical Laboratory Rock Strength Test Data Br. No. 57-1208R GL08-041, dated May 2, 2008
BB.  Geotechnical Laboratory Rock Strength Test Data Br. No. 57-1208R GL08-156, dated October 28, 2008
GG._Point Load Test San Luis Rey Br. No. 57-1208R, dated November 25, 2008

 Question= In addition to viewing the rock cores and strength test data, we would like to request copies of any and all other information the state possesses or has access to regarding the geotechnical conditions at the proposed bridge location.

  • For "Copies of any and all other information the State possesses or has access to regarding the geotechnical conditions at the proposed bridge location", bidders should contact Natalie Cornell, who manages the Geotechnical Services file room. She can make arrangements to view or obtain copies of any available geotechnical information the bidders wish to review.
  • Please contact Natalie by email at: GS_File_Room@dot.ca.gov
  • Section 2-1.03 of the Standard Specifications, paragraph 2 paragraph 3 states:
    Where there has been prior construction by the Department or other public agencies within the project limits, records of the prior construction that are currently in the possession of the Department and which have been used by, or are known to, the designers and administrators of the project will be made available for inspection by bidders or Contractors, upon written request, subject to the conditions hereinafter set forth.  The records may include, but are not limited to, as-built drawings, design calculations, foundation and site studies, project reports and other data assembled in connection with the investigation, design, construction and maintenance of the prior projects.
  • Additional historical information available: Log of Test Borings existing San Luis Rey River Br. No. 57-0957
 Question= Can the state have this additional documentation available for our visit on 10-15-09?  Please advise.
    • No, please submit your request to Natalie.

37

  Q:10/13/09

R:10/14/09

R: 10/15/09

The 10/15/09

Reply was
updated on
R:10/26/09

The 10/26/09
Reply was
updated on
R:10/27/09

Plan Sheet / Specification Reference= Hwy 76 from 0.8KM West of Melrose Drive to 1.0KM East of S. Mission Road

 Question= Page 7 of the issued Foundation Report Memorandum for Br. #57-1211 dated January 15, 2009 states that the rock cores and rock strength test data are available for viewing.  We are schedule to view both on 10-15-09.

  • There is not any Rock Strength Test Data, we do have Point Load Test and Laboratory Test Results available for BR. #57-1211. Click Here for Test Data

Additional test data documents available for BR. No. 57-1211. Please click the links below:


 Question= In addition to viewing the rock cores and strength test data, we would like to request copies of any and all other information the state possesses or has access to regarding the geotechnical conditions at the proposed bridge location.

  • For "Copies of any and all other information the State possesses or has access to regarding the geotechnical conditions at the proposed bridge location", bidders should contact Natalie Cornell, who manages the Geotechnical Services file room. She can make arrangements to view or obtain copies of any available geotechnical information the bidders wish to review.
  • Please contact Natalie by email at: GS_File_Room@dot.ca.gov
  • Section 2-1.03 of the Standard Specifications, paragraph 2 paragraph 3 states:
    Where there has been prior construction by the Department or other public agencies within the project limits, records of the prior construction that are currently in the possession of the Department and which have been used by, or are known to, the designers and administrators of the project will be made available for inspection by bidders or Contractors, upon written request, subject to the conditions hereinafter set forth.  The records may include, but are not limited to, as-built drawings, design calculations, foundation and site studies, project reports and other data assembled in connection with the investigation, design, construction and maintenance of the prior projects.

 Question= Can the state have this additional documentation available for our visit on 10-15-09?  Please advise.

  • No, please submit your request to Natalie.

38

  Q:10/13/09
R1:10/14/09


R2: 10/15/09


R3: 10/15/09
Plan Sheet / Specification Reference= 106, 107 and 108, CIDH Piling (Rock Socket)

 
Question= How do we obtain rock strength information?

  • See Bidder Inquiries # 36 and #37
  • For "Copies of any and all other information the State possesses or has access to regarding the geotechnical conditions at the proposed bridge location", bidders should contact Natalie Cornell, who manages the Geotechnical Services file room. She can make arrangements to view or obtain copies of any available geotechnical information the bidders wish to review.
  • Please contact Natalie by email at: GS_File_Room@dot.ca.gov
  • See Bidder Inquiries #36 and #37 above

39

  Q:10/13/09
R:10/14/09
Plan Sheet / Specification Reference= Section 10-1.65 for Materials, in particular, Concrete for CIDH piles.

 
Question= On sheet 203 of Special Provisions, it states that CIDH piling with a diameter greater than 2400mm shall conform to the requirements in "Mass Concrete for CIDH Piles" of these special provisions.  Does this include 2400mm diameter piles?...Or only piles larger than 2400mm? The way this is currently written, we would only apply the "Mass Concrete" requiremtns to the 2700mm portion of CIDH piles at Piers 4, 5, & 6, which are encased in permanent steel casing. Is this Caltrans intent?

  • Please bid per the contract documents.

40

  Q:10/13/09
R:10/14/09
Plan Sheet / Specification Reference= Highway 76 from 0.8KM West of Melrose Drive to 1.0KM East of South Mission Road

Question= Is caving anticipated within the limits of the rock sockets?
  • The bidders should refer to the Construction Consideration sections in the foundation reports. Actual amount/magnitude of caving will be dependant on the methods and means the contractor chooses to advance the excavation in the rock socket zones. Bidders should also refer to the Log of Test Borings at each bridge location.

41

  Q:10/14/09
R:10/15/09
Plan Sheet / Specification Reference= Special Provisions, Section 10-4.21 Water Meter, Page 337, 1st paragraph,

Question= Special Provisions, Section 10-4.21 Water Meter, Page 337, 1st paragraph, second sentence states that the Contractor shall install the concrete meter box & meters within the RMWD jurisdiction, and the City of Oceanside will install the meter and meter box within their jurisdiction. The third paragraph, first sentence states that the City of Oceanside has established a fee of $60,000.00 and the RMWD has established a fee of $80,000.00 for furnishing and installing a water meter. There is a conflict on the RMWD jurisdiction. Please Clarify.
  • RMWD will furnish water meter only - they will not install it or the meter box. The City of Oceanside will furnish and install the water meter and meter box. There is no change in the fees listed.

42

  Q:10/14/09
R:10/15/09
Plan Sheet / Specification Reference= Bid Items 106, 107, & 108.  Special Provisions sheet 159, Section 10-1.41, Rock Excavation (Controlled Balsting)

Question= Is excavation of CIDH pile "rock sockets" by controlled blasting (per the above specs.) an acceptable method?
  • No.

43

  Q:10/14/09
R:10/22/09

Plan Sheet / Specification Reference= Plan Sheets: L-12, R-1, R-2, R-3.

Question= This is a clarification for question number 7.  The cross sections that were released for the "ORR Line" on 10-6-09 are not reflective of the retaining wall 1 plan drawings.  The wall represented in the cross sections show a much smaller wall in length and in height. 
Are revised plans and cross sections coming out before or after the bid for this road and retaining wall?

  • See Addendum No. 1

44

  Q:10/14/09
R:10/15/09
Plan Sheet / Specification Reference=

Question= Your response to Question 35 doesn’t seem reasonable.  Are you suggesting that the variable overlay is between 1.95” and 17.55’ thick? That would be the conversion for .05M to .45M.  On the other hand if it was .05’ to .45’ then it would be .6” to 5.4” which would make more sense.

  • 0.05m = 0.16 foot = 1.96 inches
  • 0.45m= 1.48 foot = 17.75 inches
  • The thicker overlay is proposed at several locations where there is challenging traffic control

45

  Q:10/14/09
R:10/15/09
R: 10/21/09
Plan Sheet / Specification Reference= Bid Items 109, 110, 111 - Permanent Steel Casing.  Special Provisions page 210, "Permanent Steel Casing Installation".

Question= The answer to Bidder Inquiry will become extremely important relative to Special Provisions page 68 Section 10-1.01.  Do you have a time frame in which you intend to answer Inquiry 5?
  • An answer is pending for no later than close of business Tuesday, Oct. 20th.
  • Bidder Inquiry 5 has been answered.

46

  Q:10/14/09
R:10/22/09

Plan Sheet / Specification Reference=

Question= I am taking off the bridge deck drain system. I cannot find the thickness of the pipe of the deck drain pipe. How thick is the 200mm and 600mm pipe?

  • NPS 8 Schedule 10

47

  Q:10/14/09
R:10/20/09
Plan Sheet / Specification Reference= Good Faith Effort Documentation

Question= Should the Good Faith Effort Documentation go with the Bid Proposal or is it to be submitted on another day.
  • See Addendum No. 1 in Section 2-1.03 under:         

"Good Faith Efforts Submittal"

If good faith efforts documentation is not submitted with the bid, it must be received by the Department no later than 4:00 p.m. on the 4th business day after bid opening.

48

  Q:10/15/09
R:10/20/09
Plan Sheet / Specification Reference= Bid Items # 100 thru # 111, CIDH Piles for Piers 7, 8, & 9 @ San Luis Rey River Bridge.  Plan Sheet #1115.  Column Details No. 3

Question= There is a conflict on vertical reinforcing for the CIDH pile/column cage.  Section 'A-A' shows #36 and Sections "B-B" and "C-C" show #43?  Please clarify.
  • Use # 43

49

  Q:10/15/09
R:10/15/09
Plan Sheet / Specification Reference= Reference sheets PL-1 and PL-2

Question= On sheets PL-1 and PL-2, certain plantings are missing an on-center designation; ie: Artemisia palmeri, Iva hayesiana, etc.  Is it the intention of the agency that the plant quantities listed shall take precedence over on-center spacings?
  • The quantity of these plants planted in a area will be as shown on the plans and planted according to the note #11 on PL-1 ("RANDOMLY PLANTED THROUGHOUT ENTIRE DESIGNATED AREA, AS UNDERSTORY PLANTING FOR TREES AND SHRUBS.")

50

  Q:10/15/09
R:10/23/09
Plan Sheet / Specification Reference= Pre-Bid Meeting

Question= At the pre bid meeting, Caltrans stated that no scrapers will be allowed to cross SR76 travelled way. What section of the Special Provisions or Standard Specifications prohibits this.

For clarification of information provided at the Pre-Bid Meeting: There are two (2) traffic charts provided in Section 10-1.24 "MAINTAINING TRAFFIC", of the Special Provisions that allow transverse crossing of SR-76, in addition to the closure charts and all other safety and traffic requirements of the Special Provisions the Contractor shall submit a plan in accordance with Section 7-1.02 "LOAD LIMITATIONS", of the Standard Specifications.
In the plan the Contractor shall include:
1.) Protection measures,
2.) Contingency measures to provide enough personnel and equipment to ensure that the roadway is clear within the one (1 ) minute allowed.


51

  Q:10/15/09
R:10/20/09

Plan Sheet / Specification Reference= #69 - Plant Group T - Native Sod

Question= Per the special provisions specifications on the above Sod I am
having a hard time finding someone who will grow this.  Do you have any
suggestions?
Here are some possible suppliers for Bid Item No. 69: HIGHWAY PLANTING cost break-down item PLANT (GROUP T) NATIVE SOD:

Delta Bluegrass Company
(800) 637-8873

S&S Seeds
(805) 684-0436

Am-Sod
(800) 553-8328

RECON Native Plants
John Holt
(619) 423-2284

Capital Wholesale
(408) 239-0589


52

  Q:10/16/09
R:10/20/09
Plan Sheet / Specification Reference= #69 Plant Group T - Native Sod.

Question= In regards to question number 51: our supplier said "this seed
mix will not work for sod production. It does not have the make up to
hold together during harvest, transport and install. It would also cause
other production problems at a sod farm. This seed mix would need to be
hydroseeded on site."
  • See Bidder Inquiry No. 51 for PLANT (GROUP T) NATIVE SOD suppliers.
  • Hydroseeding will not be allowed, the methods to supply the native sod are defined per Section 10-2.04 HIGHWAY PLANTING Subsection NATIVE (SOD) on page 273 of the Special Provisions.

53

  Q:10/16/09
R:10/20/09
Plan Sheet / Specification Reference= 116 Structural Concrete Retaining Wall, 884 (R-3)

Question=
1)Could you please confirm your quantities for RW-1 shown on sheet 884 (R-3)?
  • See Addendum No. 1.
2)Anti-Graffiti coating is shown on the Architectural Treatment detail on sheet 884 (R-3) but there is no pay item or a provision for payment in the special provisions. Therefore, we are assuming that anti-graffiti coating is not required for this project.
  • Correct, there is no bid item for anti-graffiti coating. If required a CCO will be issued.

54

  Q:10/20/09
R:10/20/09
Plan Sheet / Specification Reference= Addenda

Question= When can we expect a revised Bid Schedule and the Addenda
confirming the rsponses to the "Bidders Inquiries"?
  • The bid opening date remains the same.
  • We are attempting to provide the Addendum by COB today with a revised BID ITEM LIST.

55

  Q:10/20/09
R:10/20/09
Plan Sheet / Specification Reference= Addenda

Question= Due to the lack of information for the Sanitary Force Main
Relocation is it possible to bid this relocation Bid Item # 181 as an
allowance item?
  • No, see Addendum No. 1.

56

  Q:10/20/09
R:10/20/09
Plan Sheet / Specification Reference= Rock Slope Protection

Question=The RSP quantities appear to vary more than 25 % between the
stamped Q Sheets, Plan & Profile Sheets, and Drainage Detail Sheets  for
Bid Items # 188,189,190,191 & 192.
  • The QUANTITY SHEETS are stamped and match the quantities on the BID ITEM SHEET. The Plans, Profiles and Drainage Detail sheets are not stamped and are subject to change by the Design Sequencing method per SECTION 1 of the Special Provisions, see schedule of Sequences for when the complete stamped plans will be provided.
Will the sheets be corrected and the Bid Schedule changed?
  • No, not by the proposed Addendum No. 1.

57

  Q:10/20/09
R:10/22/09

Plan Sheet / Specification Reference= Bid Items #171,172&174 - Handholes at joints

Question= Do you really want handholes at each joint?
Northwest Pipe Company does not recommend it.

  • Please bid per the contract documents.

58

  Q:10/20/09
R:10/22/09

Plan Sheet / Specification Reference= Bid Items#174 (200 mm CML&C pipeline)

Question= Can not find on the plans this pipeline. (200 mm CML&C pipeline)
Dwg UQ-3 is referencing dwg U-41
U-41 shows only the 300 mm pipeline
Please advise.

  • See Addendum No. 1

59

  Q:10/20/09
R:10/22/09

Plan Sheet / Specification Reference= Bid Items#185 (760 mm Casing) Sewer Casing

Question= There is no sewer casing speciffication for this project
Please advise

  • See Addendum No. 1

60

  Q:10/20/09
R:10/22/09

Plan Sheet / Specification Reference= Bid Items#171,172&174 (300mm, 400mm & 200 mm CML&C pipeline) Wrong quantities on UQ-3

Question=
Dwg UQ-3 is referencing the wrong U drawings for the corresponding water
lines.
The quantities shown on UQ-3 does not match the quantities shown on the U
drawings.
The pipe quantities from the bid schedule do not match the quantities shown on
the U drawings
Please submit revise the drawings to reflect the correct quantities.

  • See Addendum No. 1

61

  Q:10/20/09
R:10/22/09

R:10/23/09

Plan Sheet / Specification Reference= Bid Items#163 (600 mm Casing) Coating Speciffication

Question= All previous Caltrans Specifications requires an extra Cement Mortar Coating
over the initial coating (per AWWA C213 or AWWA C214)
Are you sure that no second coating is needed to protect the AWWA C214 coating?
Please advise

  • Please bid per the contract documents.
  • See Section 10-1.77 "Welded Steel Pipe Casing (Bridge)" of the special provisions.

62

  Q:10/20/09
R:10/23/09
Plan Sheet / Specification Reference= Bid Items#163 (600 mm Casing) Lining Speciffication

Question= The project specifications do not address linings but reference Section 70-
1.02B Welded Steel Pipe Caltrans specifications.
Please confirm that the Lining is coal tar per Section 70-1.02B
  • Please refer to Section 10-1.77 "Welded Steel Pipe Casing (Bridge)" of the special provisions.

63

  Q:10/20/09
R:10/20/09
Plan Sheet / Specification Reference= Foundation Report, dated December 11, 2008 for San Luis Rey River Bridge.  Page 12, Item #10.

Question=This Geotechnical report states "The use of rotator or oscillator methods for drilling of CIDH piles shall not be allowed."  This statement is not support in the special provisions (Section 10-1.65) for Piling. 

1. Therefore, will it be enforced in the construction of the CIDH piles for this bridge structure and not be allowed?
  • Yes.
2. This same geotechnical question is not mention in the report for Ostrich Farms Creek Bridge.  Does it also apply to CIDH pile construction for this bridge structure?
  • Yes.

64

  Q:10/20/09
R:10/21/09
Plan Sheet / Specification Reference= Item # 200; Wildlife Fence, Section
#80 Std Plans, Section 10-1.99 Chain Link Fence Special Provision.


Question= Special Provision Section 10-1.99 Chain Link Fence:
Calls for Fabric, Posts and all Hardware to be painted dark brown
closely matching ICI 454-148, Cordwood.
Does Caltrans really want a non industry standard painted chain link
fence and accessories? Typicaly they go with a Class B bonded vinyl
coated fabric, conforming to the requirements in AASHTO Designation: M
181.
The post and accessories can also be vinyl coated.
  • Please bid per current contract documents.

65

  Q:10/21/09
R:10/21/09
Plan Sheet / Specification Reference= San Luis Rey River Bridge and Ostrich Farm Creek Bridge Piers. 10-1.65 Page No. 211 Sub-Heading Paragraph No. A.  Specific (quote portion of specials, if needed): If a permanent steel casing tip elevation above a CIDH concrete piling (rock  Socket) is lowered….

     

Question=   Who determines when a permanent steel casing tip elevation is to be lowered?
  • The Engineer.

66

  Q:10/14/09
R:10/22/09

Plan Sheet / Specification Reference= Bid Items 100 thru 111. CIDH Concrete Piling LOTB's.  Contract plan sheets 1149 thru 1160, and sheets 1199 and 1203.

Question= Are there any photos of the 'rock cores' and/or core samples avaiable?  If so, can they be posted on line for viewing?

  • See Bidder's Inquiry #2.

67

  Q:10/14/09
R:10/23/09
Plan Sheet / Specification Reference= Bid Items #100 thru #111, CIDH Piles rebar cages.  Contract plan sheets 1107, 1113, 1114, 1115, & 1193.

Question= The current rebar cages for the CIDH piles for this project do not met Caltrans current Bridge Design criteria for reabr window spacing. The design requirement calls for "clear spacing of at least five times the size of the maximum course aggregate, but not less than 5 inches clear (5" X 5"). The current rebar cages must be address to avoid resticting the flow of concrete to the outside of the cage.  If not, it may result in anomaly readings during the GGL testing, which would be the responsibilty of the owner if left unaddressed.
The follwoing rebar cages have clear spacing issues;
San Luis Rey River Bridge:
1. Plan Sheet 1107,Abutment 1, 1.2M CIDH piles; Hoops @ 100mm
2. Plan Sheet 1113,Piers 2 & 3, 1.8M CIDH piles; Hoops @ 125mm, with #7 bar ties, the clear spacing would be 4".
3. Plan Sheet 1114,Piers 4,5, & 6, 2.4M CIDH piles; Hoops @ 75mm, this leaves only 2" clearance between the hoops.
4. Plan Sheet 111,Piers 7, 8, & 9, 1.8M CIDH piles; Hoops @ 75mm, same as above.

Ostrich Farm Creek Bridge
5. Plan Sheet 1193,Abutments 1 & 2, 1.2M CIDH piles; Hoops @ 100mm, again, not acceptable.
  • A CCO will be issued in accordance with Section 4-1.03 of the Standard Specifications to revise the spacing of the bar reinforcing steel shown on the plans. There will be no quantity change for Bid Item #129, Bar Reinforcing Steel (Bridge).

68

  Q:10/14/09
R:10/22/09

R:10/23/09

R:10/27/09


Plan Sheet / Specification Reference= Bid Items #100 thru #111, All CIDH Piles rebar cages. Contract plan sheets 1107, 1113, 1114, 1115, & 1193.  Location of PVC Inpsection tubes.

Question= In all cases, the inspection tubes are shown placed against the cage hoops with 75mm (3" clr.) spcing from adjacent vertical reinforcing bar.We understand that this conforms to Caltrans recently changed MEMO to Designers 3-1, which was amended back in December of 2008.  However, it does not met the Bridge Design Memo for 5" X 5" windows. One may argue that the inspect tubes are PVC and not steel, but they are both vertical members of the cage, which at as obstruction and restrict the follow of concrete to the outside of the rebar cage.
Therefore, will the PVC inspection tubes be allowed to be moved away from the hoops and vertical rebar and supported on "special" rebar chiars 3" clear from the vertical reinforcing bars?  This method has been the standard of practice and utilized in this District, successfully, over the past 5 years on numerous projects built in San Diego.  This project should be no different.

  • Special Rebar Chairs will be allowed by written approval from the Engineer.
  • Since the inspection pipes are shown schematically on the plans the following condition applies per Section 10-1.65 PILING of the Special Provisions (on page 212) under subsection: Acceptance Testing and Mitigation

            "The following additional requirements apply if inspection pipes are not shown on the plans:

D.    Where the dimensions of the pile reinforcement do not permit inspection pipes to be placed per these requirements, a
    plan for tube placement shall be submitted to the Engineer for approval in the Pile Placement Plan with a request for
    deviation before fabricating pile reinforcement."

  • Please bid per current contract documents.

69

  Q:10/21/09
R:10/27/09
Plan Sheet / Specification Reference=   San Luis Rey River Bridge and Ostrich Farm Creek Bridge Piers. Table of Contents heading to which issue pertains :10-1.65

Question= Is a CIDH construction joint allowable at the tip elevation of the permanent steel casing? 
  • No, a construction joint is not allowed at the casing tip elevations.

70

  Q:10/21/09
R:10/26/09
Plan Sheet / Specification Reference=  232 - Signal and Lighting (temp loc 1)

Question= What is in this bid item. Does the staging plans reflect the bid item per the location?
Due to the Design Sequencing bid process there will be no further information provided before bid opening. Bidders should base their bids on work shown on the plans and/ or defined in the special provisions that is quantifiable.  
  • Due to the Design Sequencing bid process there will be no further information provided before bid opening. Bidders should base their bids on work shown on the plans and/ or defined in the special provisions that is quantifiable.

71

  Q:10/21/09
R:10/26/09
Plan Sheet / Specification Reference=  Bid Item #232 Signal and Lighting(Temporary Location 1)

Question= What material is bid item #232 to contain as there does not appear to be plan sheet for and temporary work at location 1?
  • Due to the Design Sequencing bid process there will be no further information provided before bid opening. Bidders should base their bids on work shown on the plans and/ or defined in the special provisions that is quantifiable. 

72

  Q:10/21/09
R:10/26/09
Plan Sheet / Specification Reference=  Stage Construction Plan Sheets E-57 through E-65 (Pages 1021 through 1030)

Question= Under which bid item numbers shall the temporary materials for the stage consruction be placed for the Signal and Lighting Locations 2, 3, 5 and 7?
  • Stage Construction or Temporary materials should be placed under the signal and lighting system at the same locations: 
  •     Stage Construction at location 2 (E-57 & E-58) is under bid item #234
  •     Stage Construction at location 3 (E-59 & E-60) is under bid item #235
  •     Stage Construction at location 5 (E-61, E-62, & E-63) is under bid item #237
  •     Stage Construction at location 7 (E-64 & E-65) is under bid item #239

73

  Q:10/21/09
R:10/22/09

Plan Sheet / Specification Reference=  92, HOT MIX ASPHALT

Question= As the State is aware, the mix verification process for HMA has been problematic at best. Taking into account the difficulties currently being experienced by majority if not all asphalt suppliers in achieving CalTrans mix verification in District 11, will there be any allowances or variance from the Section 39 HMA process for asphalt produced on-site?  Similarly, will there be any variance given if "on-site" aggregate materials are ingredients for the HMA production?

  • NO, there will be no variance.

74

  Q:10/21/09
R:10/23/09

Plan Sheet / Specification Reference= Bid Items #163 Pipe Casing (Bridge) wall thickness
 

Question= There is no wall thickness specified or called out on the drawings for this bid item.
Please advise

  • There is an inconsistency between plans and special provisions.  Please refer to Note * in PLAN view on Plan Sheets 1105/1204 and 1106/1204.

75

  Q:10/21/09
R:10/23/09

Plan Sheet / Specification Reference= Bid Items #163 Pipe Casing (Bridge) Linings and Coatings
 

Question= I have noted that you are asking to use AWWA C213 for lining and casing . C213 is fusion bonded epoxy (Paragraph 10-1.51, page 80)
Also the same specification refers to Section 70-1.02B of the Caltrans Standard Specification. Section 70-1.02B has a coal tar (AWWA C203) requirement for linings and coatings.
All past Caltrans project were specified with Coal Tar (C203) lining and coatings and an extra overcoat of Cement Mortar Coating (per AWWA C-205)
1) Please confirm that the project specifications are correct and C213 is not a typo error.

  • Please refer to Section 10-1.77 "Welded Steel Pipe Casing (Bridge)" of the special provisions and bid per the contract documents.

2) The C214 (tape wrap) alternate coating to C213 is an 80 mills three layers tape which can be easily damaged during shipping or installation. Most of the specifications require an extra overcoat of Cement Mortar Coating (per AWWA C-205) as protection.
Please review and advise.

  • Please refer to Section 10-1.77 "Welded Steel Pipe Casing (Bridge)" of the special provisions and bid per the contract documents.

76

  Q:10/21/09
R:10/23/09

Plan Sheet / Specification Reference= Bid Items #109,110,111 Permanent Steel casing wall thickness.
 

Question= There is no wall thickness specified or called out on the drawings for these bid items.
Please advise

  •  There is no requirement on minimum wall thickness for these casings.   The contractors shall bid these items based on the constructability of the CIDH concrete piles.

77

  Q:10/22/09
R:10/27/09

Plan Sheet / Specification Reference= Items #109 through 111, CIDH Concrete Piling/, San Luis Rey River Bridge and Ostrich Farm Creek Bridge Piers/ Section 10-1.65

Question=

1) With regards to the answer to bid inquiry #65, when will the determination be made by            
  the engineer to lower the permanent steel casing?      

  • The determination will be made by the Engineer to lower the permanent steel casing during the placement of casing.

2) Will the contractor be compensated for standby time related to waiting on longer casing 
   and modifying the rebar cage for the added length of the CIDH piling if the casing is lowered?

  • Please refer to "Measurement and Payment (Piling) on page 218, under Section 10-1.65 "Piling," of the special provisions.

3) Will the added quantity of CIDH concrete piling be compensated based on bid unit pricing?

  • Please refer to "Measurement and Payment (Piling) on page 218, under Section 10-1.65 "Piling" of the special provisions.

78

  Q:10/21/09
R:10/28/09

Plan Sheet / Specification Reference= 92, HOT MIX ASPHALT

Question= Is the State aware if anyone in District 11 has been successful in obtaining mix verification for same mix and Section 39 requirements as this project specifies using an on-site plant?
Likewise, is the State aware of any fixed plant site in District 11 having achieved mix verification for mix required by this contract?
The question is posed whether that plant be supplied with aggregate materials from a local manufacturer or with materials extracted on-site on any previous or current projects.
If the answer is yes, please clarify project receiving mix verification.

  • Please bid per the contract documents.

79

  Q:10/23/09
R:10/27/09

Plan Sheet / Specification Reference= Bid items #109, 110, & 111, Special Provsisons sheet 180..."Casings"

Question= Permanent casings are to exterior surfaces coated per ANSI/AWWA C213 or 214.  What is the pruposes of this?  How does the State expect this to work if the casings are Oscilater or Vibrated in place?

  • No, Section 10-1.51 WATER SUPPLY LINE (BRIDGE) as shown on sheet 180 of the Special Provisions does not apply to Items # 109, # 110 and # 111. Please refer to Section 10-1.65 PILING of the Special Provisions.  
80
  Q:10/23/09

R:10/28/09

Plan Sheet / Specification Reference=

Question= The staging plans do not appear to cover any of the overlay on the existing SR76.  When is this overlay to occur? Will it all be at the same time?

  • Due to the Design Sequencing bid process there will be no further information provided before bid opening. Bidders should base their bids on work shown on the plans and/ or defined in the special provisions that is quantifiable.
 
81
  Q:10/26/09

R:10/27/09
 Plan Sheet / Specification Reference=   109 through 111  CIDH Concrete Piling   San Luis Rey River Bridge and Ostrich Farm Creek Bridge Piers

Question=

With regards to the response to bidder’s inquiry #37, we were notified by the Geotechnical Services File Room that all geotechnical information had been made available to bidders. We then received an email dated 10/23/09 stating that additional records may also be available for viewing in Sacramento.  Is Caltrans going to postpone the bid date to allow bidders to schedule visits to view and analyze this additional information prior to bid time?  Please advise.

 

  • No. The bid opening will not be postponed.
  • Section 2-1.03 of the Standard Specifications, paragraph 4 states:
    · Inspection of the records of investigations and project records may be made at the office of the district in which the work is situated, or in the case of records of investigations related to structure work, at the Transportation Laboratory, Sacramento, California. The records of investigations and project records are not a part of the contract and are available solely for the convenience of the bidder or Contractor.
  • Only the bidders know what information they would like to see and might be of any importance in aiding them with their bid estimates.
    The contract documents do not require the State to respond to any and all vague and burdensome requests. The contract documents do not require the State to copy any and all documents it may possess and provide them to the Bidders on demand. If a bidder does want copies of any specific documents the State may possess they may request in writing to come to the Transportation Laboratory to inspect records of investigations or rely on the California Public Records Act (CPRA), the request must be specific as to which records they want. The CPRA, clearly states that vague and burdensome requests may be denied.

 

 
82
  Q:10/27/09

R:10/28/09
Plan Sheet / Specification Reference= Spec Section 10-1.39 Earthwork

Question= Spec Section 10-1.39 third paragraph reads “Full compensation for foundation treatment  shown on the plans for drainage units shall be considered as included in the prices for the drainage unit involved” There are several drainage units which require foundation treatment outside of the foundation treatment perimeters shown on the grading sheets. What are the foundation treatment excavation limits for the drainage units located outside of the foundation treatment perimeters?
  • Please bid per current contract documents.
 
83
  Q:10/27/09

R:10/27/09
 

Plan Sheet / Specification Reference= # 200   Wildlife fence

Question= This fence is call out to be Chain Link & Toad Fence to be trenched and backfilled approx. 2' in the soil. The S.P. call for 6'high chain link fence & plan sheet # 140 calls for 10'high chain link fence what will be used?

  • Section 10-1.99 CHAIN LINK FENCE of the Special Provisions states that the fence shall be Type CL-1.8 and Type CL-3.0.
  • There is no item for Type CL-1.8.
  • Item # 200 WILDLIFE FENCE is shown on Construction Detail sheet C-31 (sheet 140 of 1204), is 10 feet.
  • 2.4 meters above ground + 0.6 meters below ground = 3.0 meters equals 8 feet above ground + 2 feet below ground = 10 feet.

Also calls to be painted Brown, will powder coated post & PVC chain link fabric be allowed?

  • Please bid per the contract documents.

Does the Toad fence have to be brown?

  • Yes, the permanent Arroyo Toad Fence shall be brown.


84
  Q:10/27/09

R:10/28/09
Plan Sheet / Specification Reference= Addendum 1 - Bid Book Page Numbering

Question= Addendum 1 requires that we replace pages 4, 5, 6, 7, 8, 9, 10, 11, 12 and 15 of the Bid Item List in the Bid book with revised pages 4, 5, 6, 7, 8, 9, 10, 11, 12 and 15.  However, the Bid book page numbers do not match the Addendum 1 page numbers for the same bid items.  Please confirm that the bidders should put the Addendum 1 pages in the correct Bid Item sequence, and not the page number order as instructed in Addendum 1.

  • Please see Addendum No. 2
85
  Q:10/27/09

R:10/28/09

Plan Sheet / Specification Reference= Item 106 through 108, CIDH Concrete Piling/San Luis Rey River Bridge and Ostrich Farm Creek Bridge Piers.

Question= The foundation report states that the rock strength data could be viewed in Sacramento with the rock cores.  Although requested at the time of viewing the rock cores, they were ultimately made available through the bidders inquiries.  Can the additional records referenced in bid inquiry #81 also be made available through the bidders inquiries?

  • No.