THE MANDATORY PREBID MEETING FOR CONTRACT 11-080104 WILL BE ON FRIDAY, SEPTEMBER 25, 2009 AT THE FOLLOWING LOCATION: 4050 TAYLOR STREET, SAN DIEGO, CA 92110
THE MEETING WILL BE HELD IN BUILDING 1, FLOOR 1, GARCIA ROOM, FROM 1:30 P.M. TO 4:30 P.M.
PLEASE CALL (619) 688-6635 WITH QUESTIONS.
| CONTRACT NO: | 11-080104 |
| ROUTE / KP | 11-SD-76-R11.7/21.1 |
| LOCATION | In San Diego County In And Near Oceanside From 0.8 Km West Of Melrose Drive To 1.0 Km East Of South Mission Road |
| DESCRIPTION | Construct A 4-lane Highway. |
| ESTIMATE | $80,000,000 |
| WORKING
DAYS |
900 |
| ADVERTISE DATE | 09/08/2009 |
| BID OPENING | 10/29/2009 |
| FINAL POSTING |
10/28/09
@ 15:00
|
The Caltrans District 11 Office is located at 4050
Taylor Street, San Diego, CA 92110. The District 11 Duty Senior
telephone number is (619) 688-6635. Please submit all inquiries
in the proper format by fax to (619) 688-6988 or e-mail to:
Duty_Senior_Const_District11@dot.ca.gov.
The responses to bidder' inquiries, unless
incorporated into a formal addenda to the contract, are not a part of
the contract and are provided for the bidder's convenience only. In
some instances, the question and answer may represent a summary of the
matters discussed rather than a word-for-word recitation. The responses
may be considered along with all other information furnished to
prospective bidders for the purpose of bidding on the project. The
availability or use of information provided in the responses to bidder'
inquiries is not to be construed in any way as a waiver of the
provisions of Section 2-1.03 of the Standard Specifications or any
other provision of the contract, the plans, Standard Specifications or
Special Provisions, nor to excuse the contractor from full compliance
with those contract requirements. Bidders are cautioned that subsequent
responses or contract addenda may affect or vary a response previously
given.
Caltrans District 11 Construction
Department has developed this method of answering Bidder's Inquiries to
better serve the needs of the Contractors who bid on our Projects.
Caltrans District 11 Construction Department will post all of the
questions submitted by any of the contractors that are registered
Planholders for that Contract, but reserves the right to not answer any
questions deemed unsatisfactory for public viewing.
The BIDDER'S
INQUIRIES & RESPONSES will be updated continuously and all attempts
will be made to do the final posting by 15:00 on Wednesday prior to the
bid opening.
INFORMATION
AVAILABLE
| INFORMATION
HANDOUT 9/14/09 |
|
|
|
|
| INFORMATION HANDOUT** provided in Addendum No. 1 on 10/20/09 |
X-SECTIONS 10/06/09 |
MANDATORY PRE-BID MEETING INFO |
||
| LOG OF BORINGS for existing Br. No. 57-0957 |
** NOTE:
The INFORMATION HANDOUT provided in Addendum No. 1 includes all the
SUPPLEMENTAL PROJECT INFORMATION (as Advertised and new documents in
Addendum No.1) per Section 5-1.08.
ORDERING
PROJECT PLANS AND SPECIFICATIONS
ADDENDA
|
|
|
BIDDER'S INQUIRY SUBMITTAL FORM
|
|
Inquiry |
|
1 Q:09/15/09 |
Plan Sheet / Specification
Reference= 120, Minor Concrete (Minor Structure), Sheet 416 Question= Drainage System 28,
Unit B & D, call out Box Culvert Wingwalls. The quantity
shown for these Wingwalls is 1550 M3 and is reflected on the Bid Item
List under Minor Concrete (Minor Structure). This quantity seems
to be a bit excessive. Please confirm that this is the correct
quantity or update the Bid Item List to reflect the correct
quantity.
|
|
2 Q:09/15/09
R:10/13/09 |
Plan Sheet / Specification
Reference= Core samples. Question= Logs of
Test Borings and Please provide contact information for the
Transportation Laboratory to view core samples.
|
|
3 R:09/21/09 |
Plan
Sheet / Specification
Reference= Question= I was wondering if I could possibly find out if this project is receiving ARRA funds. Is there a link or particular page where ARRA funded/aided projects are listed?
|
|
4 R:09/21/09 |
Plan
Sheet / Specification
Reference= Question= I did not see archaeological services listed for this project, will that be advertised somewhere else?
|
|
5 R 1:09/28/09 R 2:09/29/09 R 3: 10/20/09 |
Plan
Sheet / Specification
Reference= Bid Items 109, 110, 111 - Permanent Steel
Casing. Special Provisions page 210, "Permanent Steel Casing
Installation". Question= Will casing installation by vibratory hammer or oscillator be allowed in addition to the methods listed in the Special Provisions?
|
|
6 R:09/30/09 R:10/12/09 |
Plan
Sheet / Specification
Reference= Specials Page 70 List of Parcels Plan Sheet 26 (K-2) Question= No access dates have been provided for Parcels 33135,33136,33137. Please provide date when access will be provided.
|
|
7 R:10/07/09 |
Plan
Sheet / Specification
Reference= Plan Sheet 40 (L-12) Question= There are no Sections included in the plans for RW1 shown on Sheet L-12. Are cross sections available for that Retaining Wall.
|
|
8 R:09/30/09 |
Plan
Sheet / Specification
Reference= Special Provisions page 68 Section 10-1.01 Question= The referenced section prohibits pile driving between 2-15 and 9-15. Does this apply to drilling and pouring CIDH piling?
|
|
9 R:10/20/09 |
Plan
Sheet / Specification
Reference= Special Provisions page 147 Section 10-1.35 Question= The referenced section indicates a price of $ 11,795 good thru 7-30-2009. Should that number be considered an allowance or will Caltrans provide a new price?
|
|
10 R:10/01/09 |
Plan
Sheet / Specification
Reference= Special Provisions page 156 Section 10-1.39 Question= The referenced section indicates the possibility of stepped slopes.Portions of the job may require drill and shoot. Will stepped slopes be required in these areas?
|
|
11 R1: 10/22/09 Update to R1 R2: 10/27/09 |
Plan Sheet / Specification
Reference= Plan Sheets 454 thru 456
|
|
12 R:10/22/09 |
Plan Sheet / Specification
Reference= Utility Relocation by others pages 35 thru 38
|
|
13 R:10/15/09 |
Plan
Sheet / Specification
Reference= Utility Relocation by others pages 35 thru 38. Plan sheets U-4 thru U-8 Question= The Specials indicate SDG&E Gas will be relocating a gas line. Will fill be allowed to be placed over the top of the existing line prior to that relocation and can the line be abandoned in place?
|
|
14 R:10/20/09 |
Plan
Sheet / Specification
Reference= Plan sheets U-39 thru U-40 Question= The Specials and plans indicate that the existing AC water line is to be removed or abandoned. Both,
|
|
15 R:10/01/09 |
Plan
Sheet / Specification
Reference= Plan Sheets U-4 thru U-48 Question= 1)Have Caltrans and the Utilities completed and executed all the Joint Use Agreements (JUA's), Consent to Common Use Agreements (CCUA's), Easements or any and all Encroachment Permits required to relocate these utilities? Based on the Bid Documents it would appear that all these agreements have been executed by both parties. Please confirm.
when will the contractors have access?
|
|
16 R:10/13/09 |
Plan
Sheet / Specification
Reference= Prebid Meeting Question= At the Pre Bid meeting Caltrans indicated that a limited NTP would be granted for mowing and clearing prior to all the necessary submittals and schedules being approved so that clearing and mowing could be completed prior to 2-15. Please confirm.
2) The SWPPP Submittal for the IBP plans must be submitted and conditionally approved. 3) A SWPPP Submittal is not required for CHAIN AND MOW of the IBP area but a commitment to place BMPs as necessary during the operation based on the current field conditions at the time will be required. 4) A SWPPP Submittal is not required for CHAIN AND MOW of the Sequence 1 and 2 area but a commitment to place BMPs as necessary during the operation based on the current field conditions at the time will be required. 5) ESA fencing placed prior to CHAIN AND MOW of Sequence 2 as necessary. |
|
17 R:10/14/09 |
Plan
Sheet / Specification
Reference= Specials page 106 Section 10-1.16 Question= Temporary Water Diversion section requires the contractor to submit a Hydraulic Analysis for the San Luis Rey River prior to any diversion work. Does this analysis need to include the 562 sq miles alluded to at the pre bid or just sufficient for the contractors work.
|
|
18 R:10/22/09 R:10/23/09 |
Plan Sheet / Specification
Reference= Plan Sheets U-35 to U-48 Water Line Relocations
2. WTR-6 does not show the
existing storm drainage. Does that storm
3. What Item is the Temporary
Highline on Sheet 35 to be paid under?
4. Bid Item 174 as stated does
not match the Q heets or plans. Please
|
|
19 R:10/15/09 |
Plan
Sheet / Specification
Reference= Plan Sheets U-4 to U-5 Gas Line Relocation Question= Does the 75 MM Gas Line get relocated or is it abandoned?
|
|
20 R:10/05/09 |
Plan
Sheet / Specification
Reference= Question= "Federal conformity regulations require analysis of construction impacts when construction activities would last for more than 5 years. The proposed project would last less than 5 years; therefore, no quantitative estimates of regional construction emissions have been made." (Final Environmental Impact Report/ Environmental Impact Statement State Route 76 Melrose to South Mission San Diego County, 3-183, 2008). Are the impacts associated with operating an asphalt or a concrete plant within the right-of-way included in the exclusion for analysis of construction impacts for projects of less than 5 year duration?
|
|
21 R:10/20/09 |
Plan
Sheet / Specification
Reference= Section 2 Bidding Question= The Special Notices state: “The Department is implementing new Disadvantaged Business Enterprise requirements for Underutilized Disadvantaged Business Enterprises (UDBE). Section 2, "Bidding," under subsection titled "Disadvantaged Business Enterprises" and Section 5, "General," under subsection titled "Performance of UDBEs" of these special provisions cover the UDBE requirements.” In Section 2 “bidding” there is not a subsection titled “Underutilized Disadvantaged Business Enterprises”; In Section 5 “General” under subsection titled “Performance of UDBEs” It states: “UDBEs must perform work or supply materials as listed in the Caltrans Bidder - UDBE - Commitment form specified under Section 2, "Bidding," of these special provisions.” Section 2 Bidding contains no information regarding the Caltrans Bidder – UDBE – Commitment Form. In the Bid book the Caltrans Bidder – UDBE – Commitment states: “This information may be submitted with your bid proposal. If it is not, and you are the apparent low bidder or the second or third low bidder, it must be submitted and received as specified in Section 2 of the Special Provisions.” Again, these requirements are not addressed in Section 2. Please provide Section 2 Bidding requirements for UDBE.
|
|
22 R:10/05/09 |
Plan
Sheet / Specification
Reference= Question= The Director and County Counsel for the San Diego Air Pollution Control District (APCD) interpret the regulations for the use of portable equipment (crushers, screens, asphalt, and concrete batch plants) registered under the statewide PERP program as an absolute 12 month limitation for their use on any site ("Any engine or equipment unit such as back-up or stand-by engines or equipment units, that replace engine(s) or equipment unit(s) at a location, and is intended to perform the same or similar function as the engine(s) or equipment unit(s) being replaced, will be included in calculating the consecutive time period. In that case, the cumulative time of all engine(s) or equipment unit(s), including the time between the removal of the original engine(s) or equipment unit(s) and installation of the replacement engine(s) or equipment unit(s), will be counted toward the consecutive time period", Regulation to Establish a Statewide Portable Equipment Registration Program, Section 2452(cc)(1), 2007). APCD has determined that the 12 month time limit begins the day the equipment arrives at the site and terminates 12 months later. APCD does not recognize the legitimate removal of portable equipment from the site (not for the purpose of circumventing the rules, id at Section 2452(cc)(3)) as the end of a consecutive 12 month period (The engine or equipment unit is not portable if...the equipment will reside at the same location for more than 12 consecutive months..., id at Section 2452(cc)(1)). Projects that last more than 12 months are considered a Stationary Source. Stationary sources require an Authority to Construct with a Permit to Operate (Air pollution Control District County of San Diego, Regulation II, Rule 10 and Rule 12, 2007). Furthermore, APCD has determined that the entire project would be considered as a stationary source because the construction project takes place on one or more contiguous properties under common ownership (id at Rule 12 20.1(c)(67), "Stationary Source means an emission unit...located on the same or contiguous properties and which units are under common ownership or entitlement to use"). Will a variance for the use of portable equipment, for more than 12 months, be made available to the contractor or will the contractors have to apply for a Permit to Operate if their equipment is on the project for more than 12 months?
|
|
23 R:10/27/09 |
Plan
Sheet / Specification
Reference= Question= Under section 5-1.22 Non-highway Facilities (Utilities) of the Special Provisions, a RELOCATION schedule is listed showing Notification/Working days for each utility in each Sequence (page 35). Pages 36-38 show specific RELOCATION/INSTALLATION activities the utilities will perform, but there is no schedule of notification days required, or the number of working days required to complete these tasks. Please indicate what Notification/Working Days are required for the activities on pages 36-38.
|
|
24 R:10/22/09 |
Plan Sheet / Specification
Reference= Bid Item 174 - 200 mm Steel Cement Mortar Lined and
Coated Water Main (Class-350)
|
|
25 R:10/22/09 |
Plan Sheet / Specification
Reference= On sheet 496, Plan U-36, Approximate station 41+20.00,
it appears that there is a waterline that connects to “WTR1” and
crosses the proposed SD-76. This waterline has no call outs or
construction notes.
|
|
26 R:10/05/09 |
Plan
Sheet / Specification
Reference= Question= Can the State release a list of prime contractors that attended the mandatory Pre-Bid?
|
|
27 R:10/20/09 |
Plan Sheet / Specification
Reference= |
|
28 R:10/13/09 |
Plan
Sheet / Specification
Reference= Item# 73 Erosion Control Type D Seed Mix Question= We are seed suppliers of Native seed in California. I am trying to give prices and seed availability to my customers, who sub-contract the erosion control for this project. This question pertains to page 166-167. The plans indicate 47 hectares for erosion control type D seed mix, but the pages list 3 different seed mixes under that category. (Seed Type 1, 2, & 3) I need to know the area size for each of these seed mixes so I may determine the amount of seed that would be needed for each mix. You may either let me know in total Kgs per mix or total hectares per mix.
|
|
29 R:10/15/09 |
Plan
Sheet / Specification
Reference= Item 148, Sheet 325, Drainage Profile for Drainage Plan 26B Question= Is there a drainage profile for drainage system 26B? The layout drawings do not provide enough information.
|
|
30 R:10/14/09 |
Plan
Sheet / Specification
Reference= Sanitary Sewer SSD-1 Question= Are these Manholes to be T-Lok or plain as indicated?
|
|
31 R:10/13/09 |
Plan
Sheet / Specification
Reference= Storm Drain System 3 DP-2A Question= Indicates work by others, who & when?
|
|
32 R:10/15/09 |
Plan
Sheet / Specification
Reference= Storm Drain Issues. Please clarify and revise accordingly Question= 1. System 70 a & b plan & profile do not match the quantity sheet.
Please revise the quantities for this system.
12. Bid Item 169 does not appear to be a correct quantity.
|
|
33 R:10/15/09 |
Plan
Sheet / Specification
Reference= Bid Item # 48, Plan Sheet 869 Question= Bid Item # 48 Cold Plane Asphalt Concrete Pavement has a quantity of 24,100 M2, Plan Sheet 869 provides a summary with the locations for the Cold Plane Work. Can you please provide the Cold Plane limits from station 181+60 to 193+00, and also from 203+50 to 207+00. The Layout Sheets don’t show the Cold Plane limits matching the quantities shown on sheet 869 for the mentioned stationing.
|
|
34 R:10/12/09 |
Plan
Sheet / Specification
Reference= Cross Sections Question= Regarding cross sections posted 10/6/09, were there any changes made to previoulsy posted sections? If so, what stations were changed?
|
|
35 R:10/13/09 |
Plan
Sheet / Specification
Reference= On sheet No.2 under the 'Typical Structural Sections'
No.7 Question= On sheet No.2 under the 'Typical Structural Sections' No.7 indicates a variable HMA overlay and ( 0.05-0.45). Is this to be interpreted as mm or is this in feet?
|
|
36
Q:10/13/09
R:10/14/09 R:10/15/09 The 10/15/09 Reply was updated on R:10/26/09 The 10/26/09 Reply was updated on R:10/27/09 |
Plan
Sheet / Specification
Reference= Foundation
Report Memorandum for Bridge #57-1208R
(12/11/08) Question= Page 10 of the issued Foundation Report Memorandum for Br. #57-1208R dated December 11, 2008 states that the rock cores and rock strength test data are available for viewing. We are schedule to view both on 10-15-09.
Y. Geotechnical Laboratory Rock Strength Test Data Br. No. 57-1208R GL08-017, dated April 15, 2008 Z. Geotechnical Laboratory Rock Strength Test Data Br. No. 57-1208R GL08-038, dated May 13, 2008 AA. Geotechnical Laboratory Rock Strength Test Data Br. No. 57-1208R GL08-041, dated May 2, 2008 BB. Geotechnical Laboratory Rock Strength Test Data Br. No. 57-1208R GL08-156, dated October 28, 2008 GG._Point Load Test San Luis Rey Br. No. 57-1208R, dated November 25, 2008 Question= In addition to viewing the rock cores and strength test data, we would like to request copies of any and all other information the state possesses or has access to regarding the geotechnical conditions at the proposed bridge location.
|
|
37
Q:10/13/09
R:10/14/09 R: 10/15/09 The 10/15/09 Reply was updated on R:10/26/09 The 10/26/09 Reply was updated on R:10/27/09 |
Plan
Sheet / Specification
Reference= Hwy
76 from 0.8KM West of Melrose Drive to 1.0KM East of S. Mission Road Question= Page 7 of the issued
Foundation Report Memorandum for
Br. #57-1211 dated January 15, 2009 states that the rock cores and rock
strength test data are available for viewing. We
are schedule to view both on 10-15-09.
Additional test data documents available for BR. No. 57-1211. Please click the links below:
Question= In addition to viewing the rock cores and strength test data, we would like to request copies of any and all other information the state possesses or has access to regarding the geotechnical conditions at the proposed bridge location.
|
|
38
Q:10/13/09
R1:10/14/09 R2: 10/15/09 R3: 10/15/09 |
Plan
Sheet / Specification
Reference= 106, 107 and 108, CIDH Piling (Rock Socket) Question= How do we obtain rock strength information?
|
|
39
Q:10/13/09
R:10/14/09 |
Plan
Sheet / Specification
Reference= Section 10-1.65 for Materials, in particular, Concrete for
CIDH piles. Question= On sheet 203 of Special Provisions, it states that CIDH piling with a diameter greater than 2400mm shall conform to the requirements in "Mass Concrete for CIDH Piles" of these special provisions. Does this include 2400mm diameter piles?...Or only piles larger than 2400mm? The way this is currently written, we would only apply the "Mass Concrete" requiremtns to the 2700mm portion of CIDH piles at Piers 4, 5, & 6, which are encased in permanent steel casing. Is this Caltrans intent?
|
|
40
Q:10/13/09
R:10/14/09 |
Plan
Sheet / Specification
Reference= Highway 76 from 0.8KM
West of Melrose Drive to
1.0KM East of South Mission Road
|
|
41
Q:10/14/09
R:10/15/09 |
Plan
Sheet / Specification
Reference= Special Provisions,
Section 10-4.21 Water Meter, Page 337, 1st paragraph, Question= Special Provisions, Section 10-4.21 Water Meter, Page 337, 1st paragraph, second sentence states that the Contractor shall install the concrete meter box & meters within the RMWD jurisdiction, and the City of Oceanside will install the meter and meter box within their jurisdiction. The third paragraph, first sentence states that the City of Oceanside has established a fee of $60,000.00 and the RMWD has established a fee of $80,000.00 for furnishing and installing a water meter. There is a conflict on the RMWD jurisdiction. Please Clarify.
|
|
42
Q:10/14/09
R:10/15/09 |
Plan
Sheet / Specification
Reference= Bid Items 106, 107, & 108. Special Provisions
sheet 159, Section 10-1.41, Rock Excavation (Controlled Balsting) Question= Is excavation of CIDH pile "rock sockets" by controlled blasting (per the above specs.) an acceptable method?
|
|
43
Q:10/14/09
R:10/22/09 |
Plan Sheet / Specification
Reference= Plan Sheets: L-12, R-1, R-2, R-3.
|
|
44
Q:10/14/09
R:10/15/09 |
Plan
Sheet / Specification
Reference= Question= Your response to Question 35 doesn’t seem reasonable. Are you suggesting that the variable overlay is between 1.95” and 17.55’ thick? That would be the conversion for .05M to .45M. On the other hand if it was .05’ to .45’ then it would be .6” to 5.4” which would make more sense.
|
|
45
Q:10/14/09
R:10/15/09 R: 10/21/09 |
Plan
Sheet / Specification
Reference= Bid Items 109, 110, 111 - Permanent Steel Casing.
Special Provisions page 210, "Permanent Steel Casing Installation". Question= The answer to Bidder Inquiry will become extremely important relative to Special Provisions page 68 Section 10-1.01. Do you have a time frame in which you intend to answer Inquiry 5?
|
|
46
Q:10/14/09
R:10/22/09 |
Plan Sheet / Specification
Reference=
|
|
47
Q:10/14/09
R:10/20/09 |
Plan
Sheet / Specification
Reference= Good Faith Effort Documentation Question= Should the Good Faith Effort Documentation go with the Bid Proposal or is it to be submitted on another day.
"Good Faith Efforts Submittal" If good faith efforts documentation is not submitted with the
bid, it must be received by the Department no later than 4:00 p.m. on
the 4th business day after bid opening. |
|
48
Q:10/15/09
R:10/20/09 |
Plan
Sheet / Specification
Reference= Bid Items # 100 thru # 111, CIDH Piles for Piers 7, 8, &
9 @ San Luis Rey River Bridge. Plan Sheet #1115. Column
Details No. 3 Question= There is a conflict on vertical reinforcing for the CIDH pile/column cage. Section 'A-A' shows #36 and Sections "B-B" and "C-C" show #43? Please clarify.
|
|
49
Q:10/15/09
R:10/15/09 |
Plan
Sheet / Specification
Reference= Reference sheets PL-1 and PL-2 Question= On sheets PL-1 and PL-2, certain plantings are missing an on-center designation; ie: Artemisia palmeri, Iva hayesiana, etc. Is it the intention of the agency that the plant quantities listed shall take precedence over on-center spacings?
|
|
50
Q:10/15/09
R:10/23/09 |
Plan
Sheet / Specification
Reference= Pre-Bid Meeting Question= At the pre bid meeting, Caltrans stated that no scrapers will be allowed to cross SR76 travelled way. What section of the Special Provisions or Standard Specifications prohibits this. For clarification of information provided at the Pre-Bid Meeting: There are two (2) traffic charts provided in Section 10-1.24 "MAINTAINING TRAFFIC", of the Special Provisions that allow transverse crossing of SR-76, in addition to the closure charts and all other safety and traffic requirements of the Special Provisions the Contractor shall submit a plan in accordance with Section 7-1.02 "LOAD LIMITATIONS", of the Standard Specifications. In the plan the Contractor shall include: 1.) Protection measures, 2.) Contingency measures to provide enough personnel and equipment to ensure that the roadway is clear within the one (1 ) minute allowed. |
|
51
Q:10/15/09
R:10/20/09 |
Plan Sheet / Specification
Reference= #69 - Plant Group T - Native Sod |
|
52
Q:10/16/09
R:10/20/09 |
Plan
Sheet / Specification
Reference= #69 Plant Group T - Native Sod. Question= In regards to question number 51: our supplier said "this seed mix will not work for sod production. It does not have the make up to hold together during harvest, transport and install. It would also cause other production problems at a sod farm. This seed mix would need to be hydroseeded on site."
|
|
53
Q:10/16/09
R:10/20/09 |
Plan
Sheet / Specification
Reference= 116 Structural Concrete Retaining Wall, 884 (R-3) Question= 1)Could you please confirm your quantities for RW-1 shown on sheet 884 (R-3)?
|
|
54
Q:10/20/09
R:10/20/09 |
Plan
Sheet / Specification
Reference= Addenda Question= When can we expect a revised Bid Schedule and the Addenda confirming the rsponses to the "Bidders Inquiries"?
|
|
55
Q:10/20/09
R:10/20/09 |
Plan
Sheet / Specification
Reference= Addenda Question= Due to the lack of information for the Sanitary Force Main Relocation is it possible to bid this relocation Bid Item # 181 as an allowance item?
|
|
56
Q:10/20/09
R:10/20/09 |
Plan
Sheet / Specification
Reference= Rock Slope Protection Question=The RSP quantities appear to vary more than 25 % between the stamped Q Sheets, Plan & Profile Sheets, and Drainage Detail Sheets for Bid Items # 188,189,190,191 & 192.
|
|
57
Q:10/20/09
R:10/22/09 |
Plan Sheet / Specification
Reference= Bid Items #171,172&174 - Handholes at joints
|
|
58
Q:10/20/09
R:10/22/09 |
Plan Sheet / Specification
Reference= Bid Items#174 (200 mm CML&C pipeline)
|
|
59
Q:10/20/09
R:10/22/09 |
Plan Sheet / Specification
Reference= Bid Items#185 (760 mm Casing) Sewer Casing
|
|
60
Q:10/20/09
R:10/22/09 |
Plan Sheet / Specification
Reference= Bid Items#171,172&174 (300mm, 400mm & 200 mm
CML&C pipeline) Wrong quantities on UQ-3
|
|
61
Q:10/20/09
R:10/22/09 R:10/23/09 |
Plan Sheet / Specification
Reference= Bid Items#163 (600 mm Casing) Coating Speciffication
|
|
62
Q:10/20/09
R:10/23/09 |
Plan
Sheet / Specification
Reference= Bid Items#163 (600 mm Casing) Lining Speciffication Question= The project specifications do not address linings but reference Section 70- 1.02B Welded Steel Pipe Caltrans specifications. Please confirm that the Lining is coal tar per Section 70-1.02B
|
|
63
Q:10/20/09
R:10/20/09 |
Plan
Sheet / Specification
Reference= Foundation Report, dated December 11, 2008 for San Luis Rey
River Bridge. Page 12, Item #10. Question=This Geotechnical report states "The use of rotator or oscillator methods for drilling of CIDH piles shall not be allowed." This statement is not support in the special provisions (Section 10-1.65) for Piling. 1. Therefore, will it be enforced in the construction of the CIDH piles for this bridge structure and not be allowed?
|
|
64
Q:10/20/09
R:10/21/09 |
Plan
Sheet / Specification
Reference= Item # 200; Wildlife Fence, Section #80 Std Plans, Section 10-1.99 Chain Link Fence Special Provision. Question= Special Provision Section 10-1.99 Chain Link Fence: Calls for Fabric, Posts and all Hardware to be painted dark brown closely matching ICI 454-148, Cordwood. Does Caltrans really want a non industry standard painted chain link fence and accessories? Typicaly they go with a Class B bonded vinyl coated fabric, conforming to the requirements in AASHTO Designation: M 181. The post and accessories can also be vinyl coated.
|
|
65
Q:10/21/09
R:10/21/09 |
Plan
Sheet / Specification
Reference= San
Luis Rey River Bridge and Ostrich Farm Creek Bridge Piers. 10-1.65
Page No. 211 Sub-Heading Paragraph No. A. Specific
(quote portion of specials, if needed): If a
permanent steel casing tip elevation above a CIDH concrete
piling (rock Socket)
is lowered….
|
|
66
Q:10/14/09
R:10/22/09 |
Plan Sheet / Specification
Reference= Bid Items 100 thru 111. CIDH Concrete Piling LOTB's.
Contract plan sheets 1149 thru 1160, and sheets 1199 and 1203.
|
|
67
Q:10/14/09
R:10/23/09 |
Plan
Sheet / Specification
Reference= Bid Items #100 thru #111, CIDH Piles rebar
cages. Contract plan sheets 1107, 1113, 1114, 1115, & 1193. Question= The current rebar cages for the CIDH piles for this project do not met Caltrans current Bridge Design criteria for reabr window spacing. The design requirement calls for "clear spacing of at least five times the size of the maximum course aggregate, but not less than 5 inches clear (5" X 5"). The current rebar cages must be address to avoid resticting the flow of concrete to the outside of the cage. If not, it may result in anomaly readings during the GGL testing, which would be the responsibilty of the owner if left unaddressed. The follwoing rebar cages have clear spacing issues; San Luis Rey River Bridge: 1. Plan Sheet 1107,Abutment 1, 1.2M CIDH piles; Hoops @ 100mm 2. Plan Sheet 1113,Piers 2 & 3, 1.8M CIDH piles; Hoops @ 125mm, with #7 bar ties, the clear spacing would be 4". 3. Plan Sheet 1114,Piers 4,5, & 6, 2.4M CIDH piles; Hoops @ 75mm, this leaves only 2" clearance between the hoops. 4. Plan Sheet 111,Piers 7, 8, & 9, 1.8M CIDH piles; Hoops @ 75mm, same as above. Ostrich Farm Creek Bridge 5. Plan Sheet 1193,Abutments 1 & 2, 1.2M CIDH piles; Hoops @ 100mm, again, not acceptable.
|
|
68 Q:10/14/09 R:10/27/09
|
Plan Sheet / Specification
Reference= Bid Items #100 thru #111, All CIDH Piles rebar cages.
Contract plan sheets 1107, 1113, 1114, 1115, & 1193. Location
of PVC Inpsection tubes.
|
|
69
Q:10/21/09
R:10/27/09 |
Plan
Sheet / Specification
Reference=
San
Luis Rey River Bridge and Ostrich Farm Creek Bridge Piers. Table
of Contents heading to which issue pertains :10-1.65 Question= Is a CIDH construction joint allowable at the tip elevation of the permanent steel casing?
|
|
70
Q:10/21/09
R:10/26/09 |
Plan
Sheet / Specification
Reference=
232 - Signal and Lighting (temp loc 1) Question= What is in this bid item. Does the staging plans reflect the bid item per the location? Due to the Design Sequencing bid process there will be no further information provided before bid opening. Bidders should base their bids on work shown on the plans and/ or defined in the special provisions that is quantifiable.
|
|
71
Q:10/21/09
R:10/26/09 |
Plan
Sheet / Specification
Reference=
Bid Item #232 Signal and Lighting(Temporary Location 1) Question= What material is bid item #232 to contain as there does not appear to be plan sheet for and temporary work at location 1?
|
|
72
Q:10/21/09
R:10/26/09 |
Plan
Sheet / Specification
Reference=
Stage Construction Plan Sheets E-57 through E-65
(Pages 1021 through 1030) Question= Under which bid item numbers shall the temporary materials for the stage consruction be placed for the Signal and Lighting Locations 2, 3, 5 and 7?
|
|
73
Q:10/21/09
R:10/22/09 |
Plan Sheet / Specification
Reference=
92, HOT MIX ASPHALT
|
|
74
Q:10/21/09
R:10/23/09 |
Plan Sheet / Specification
Reference= Bid Items #163 Pipe Casing (Bridge) wall thickness
|
|
75
Q:10/21/09
R:10/23/09 |
Plan Sheet / Specification
Reference= Bid Items #163 Pipe Casing (Bridge) Linings and Coatings
2) The C214 (tape wrap)
alternate coating to C213 is an 80 mills three
layers tape which can be easily damaged during shipping or
installation. Most of the specifications require an extra overcoat of
Cement Mortar Coating (per AWWA C-205) as protection.
|
|
76
Q:10/21/09
R:10/23/09 |
Plan Sheet / Specification
Reference= Bid Items #109,110,111 Permanent Steel casing wall thickness.
|
|
77
Q:10/22/09
R:10/27/09 |
Plan Sheet / Specification
Reference= Items #109 through 111, CIDH Concrete Piling/, San Luis Rey
River Bridge and Ostrich Farm Creek Bridge Piers/ Section 10-1.65 1) With regards to the answer to bid inquiry #65, when
will the determination be made
by
2) Will the contractor be compensated for standby time
related to
waiting on longer casing
3) Will the added quantity of CIDH concrete piling be
compensated based
on bid unit pricing?
|
|
78
Q:10/21/09
R:10/28/09 |
Plan Sheet / Specification
Reference= 92, HOT MIX ASPHALT
|
|
79
Q:10/23/09
R:10/27/09 |
Plan Sheet / Specification
Reference= Bid items #109, 110, & 111, Special Provsisons sheet
180..."Casings"
|
|
80
Q:10/23/09 R:10/28/09 |
Plan Sheet / Specification
Reference=
|
|
81
Q:10/26/09 R:10/27/09 |
Plan Sheet / Specification
Reference=
109 through 111 CIDH
Concrete Piling San
Luis Rey River Bridge and Ostrich Farm Creek Bridge Piers Question= With regards to the response
to bidder’s inquiry #37, we were notified by the Geotechnical Services
File
Room that all geotechnical information had been made available to
bidders. We
then received an email dated 10/23/09 stating that additional records
may also
be available for viewing in Sacramento.
Is Caltrans going to postpone the bid date to allow bidders to schedule
visits to view and analyze this additional information prior to bid
time? Please advise.
|
|
82
Q:10/27/09 R:10/28/09 |
Plan
Sheet / Specification
Reference= Spec Section 10-1.39 Earthwork Question= Spec Section 10-1.39 third paragraph reads “Full compensation for foundation treatment shown on the plans for drainage units shall be considered as included in the prices for the drainage unit involved” There are several drainage units which require foundation treatment outside of the foundation treatment perimeters shown on the grading sheets. What are the foundation treatment excavation limits for the drainage units located outside of the foundation treatment perimeters?
|
|
83
Q:10/27/09 R:10/27/09 |
Plan Sheet / Specification
Reference= # 200 Wildlife fence
Also calls to be painted Brown, will powder coated post & PVC chain link fabric be allowed?
Does the Toad fence have to be brown?
|
|
84
Q:10/27/09 R:10/28/09 |
Plan
Sheet / Specification
Reference= Addendum 1 - Bid Book Page Numbering Question= Addendum 1 requires that we replace pages 4, 5, 6, 7, 8, 9, 10, 11, 12 and 15 of the Bid Item List in the Bid book with revised pages 4, 5, 6, 7, 8, 9, 10, 11, 12 and 15. However, the Bid book page numbers do not match the Addendum 1 page numbers for the same bid items. Please confirm that the bidders should put the Addendum 1 pages in the correct Bid Item sequence, and not the page number order as instructed in Addendum 1.
|
|
85
Q:10/27/09 R:10/28/09 |
Plan Sheet / Specification
Reference= Item 106 through 108, CIDH Concrete Piling/San
Luis Rey River Bridge and Ostrich Farm Creek Bridge Piers.
|
OTHER LINKS OF INTEREST