BIDDER'S INQUIRIES & RESPONSES
DISTRICT 11 CONSTRUCTION

 
CONTRACT NO: 11-294304
ROUTE / KP 11-SD-78-31.5
LOCATION In San Diego County Near Ramona At 1.6 Miles West Of Weekend Villa Road
DESCRIPTION Reconstruct Retaining Wall.
ESTIMATE $ 490,000
WORKING DAYS 50
ADVERTISE DATE 06/30/2008
BID OPENING 07/31/2008     09/18/2008
FINAL POSTING 09/17/08   @    1510

BID RESULTS

The Caltrans District 11 Office is located at 4050 Taylor Street, San Diego, CA 92110. The District 11 Duty Senior telephone number is (619) 688-6635. Please submit all inquiries in the proper format by fax to (619) 688-6988 or e-mail to:
Duty_Senior_Const_District11@dot.ca.gov.
The responses to bidder' inquiries, unless incorporated into a formal addenda to the contract, are not a part of the contract and are provided for the bidder's convenience only. In some instances, the question and answer may represent a summary of the matters discussed rather than a word-for-word recitation. The responses may be considered along with all other information furnished to prospective bidders for the purpose of bidding on the project. The availability or use of information provided in the responses to bidder' inquiries is not to be construed in any way as a waiver of the provisions of Section 2-1.03 of the Standard Specifications or any other provision of the contract, the plans, Standard Specifications or Special Provisions, nor to excuse the contractor from full compliance with those contract requirements. Bidders are cautioned that subsequent responses or contract addenda may affect or vary a response previously given.
Caltrans District 11 Construction Department has developed this method of answering Bidder's Inquiries to better serve the needs of the Contractors who bid on our Projects. Caltrans District 11 Construction Department will post all of the questions submitted by any of the contractors that are registered Planholders for that Contract, but reserves the right to not answer any questions deemed unsatisfactory for public viewing.
The BIDDER'S INQUIRIES & RESPONSES will be updated continuously and all attempts will be made to do the final posting by 15:00 on Wednesday prior to the bid opening.
INFORMATION AVAILABLE
 

BID ITEMS
 SPECIALS
PLANS
 PLANHOLDERS





ORDERING PROJECT PLANS AND SPECIFICATIONS

ADDENDUM


 
 
 

BIDDER'S INQUIRY SUBMITTAL FORM


Inquiry No.
Inquiry
    1 

   Q:0718/08
   R:07/25/08

Plan Sheet / Specification Reference= #19, STRUCTURAL STEEL, SHEET #10, SPEC.PROV.SECT. 10-1.25

Question= 1. ARE C10x20x9.6' SHAPES TO MADE OF GALVANIZED STOCK, STUDS WELDED AND PATCHED WITH GALVALLOY OR FABRICATED WITH PLAIN STEEL, STUDS WELDED AND ENTIRE ASSEMBLY GALVANIZED?

  • Galvanizing shall conform to Section 55-3.18 and Section 75-1.05 of the Standard Specifications.

    2. IS 1/2"x22"x9'-9.5" PLATE SHAPE PAINT ONLY, NO GALVANIZING?+
  • Yes, the plans indicate that the 0.5” x 22” plate is to be painted, therefore, no galvanizing applies. The requirements of “Clean and Paint Structural Steel” of the special provisions shall apply.

    2 

Q:07/18/08
 R:07/25/08

Plan Sheet / Specification Reference= ITEM #21, SPOT BLAST CLEAN AND PAINT UNDERCOAT, SPEC.PROV.SECT. 10-1.27

Question= IS SPOT BLASTING AND PAINTING REQUIRED FOR ALL EXISTING SURFACES OR JUST METAL EXPOSED AFTER SHOTCRETE? 

  • Spot blast cleaning and painting undercoat is required for all existing metal that is in contact with new metal. The limits of this work extend to 4 inches from the edge of contact between the metals at the welded connection.

    3 

   Q:07/25/08
   R:07/31/08

Plan Sheet / Specification Reference= 

Question= THE TIMBER LAGGING IS BOWED BETWEEN THE VERTICAL PILES. ATTACHMENT
OF THE CHANNEL TO ONE OF THE PILES WILL CAUSE THE OTHER END TO BE 2 TO 3
INCHES FROM THE PILE. THIS GAP IS TOO LARGE FOR A FILLET WELD. WHAT IS THE
PROCEEDURE TO CLOSE THIS GAP IN ORDER TO PLACE THE FILLET WELD?

  • Bid per the current details shown on the plans.

    4 

   Q:07/25/08
   R:07/31/08

Plan Sheet / Specification Reference= SHEET 10 OF TEN DETAIL A 

Question= SHEET 10 OF TEN DETAIL A

WELD ARROWS ARE POINTING TO THE BEARING PLATE OF THE TIEBACKS. THIS PLATE
WILL BE WELDED TO THE VERTICAL BEAM. HOW IS THE 1/2"X22" PLATE ATTACHED TO
THE VERTICAL BEAM?

THE WELD ARROW POINTING TO THE RIGHT SIDE OF THE BEARING PLATE INDICATES A
1/4" WELD. THERE DOES NOT APPEAR TO BE ANY BACKING FOR A FILLET WELD. IS
THIS THE CORRRECT WELD TO ATTACH TWO PLATES TOGETHER AT THIS LOCATION?

  • The weld arrows point to the weld of the 1/2" x 22" plate, around the bearing plate to the face of the existing soldier pile. There is no welding to the existing tieback bearing plate. Bid per the details shown on the plans.