BIDDER'S INQUIRIES & RESPONSES
DISTRICT 11 CONSTRUCTION

 
CONTRACT NO: 11-264804
ROUTE / KP 11-SD-5506
LOCATION In San Diego County In San Diego At The District Office Historic Building
DESCRIPTION Repair And Remodel Of District Building.
ESTIMATE $ 650,000
WORKING DAYS 125
ADVERTISE DATE 07/07/2008
BID OPENING 08/07/2008
FINAL POSTING 08/06/08   @    1520

BID RESULTS

The Caltrans District 11 Office is located at 4050 Taylor Street, San Diego, CA 92110. The District 11 Duty Senior telephone number is (619) 688-6635. Please submit all inquiries in the proper format by fax to (619) 688-6988 or e-mail to:
Duty_Senior_Const_District11@dot.ca.gov.
The responses to bidder' inquiries, unless incorporated into a formal addenda to the contract, are not a part of the contract and are provided for the bidder's convenience only. In some instances, the question and answer may represent a summary of the matters discussed rather than a word-for-word recitation. The responses may be considered along with all other information furnished to prospective bidders for the purpose of bidding on the project. The availability or use of information provided in the responses to bidder' inquiries is not to be construed in any way as a waiver of the provisions of Section 2-1.03 of the Standard Specifications or any other provision of the contract, the plans, Standard Specifications or Special Provisions, nor to excuse the contractor from full compliance with those contract requirements. Bidders are cautioned that subsequent responses or contract addenda may affect or vary a response previously given.
Caltrans District 11 Construction Department has developed this method of answering Bidder's Inquiries to better serve the needs of the Contractors who bid on our Projects. Caltrans District 11 Construction Department will post all of the questions submitted by any of the contractors that are registered Planholders for that Contract, but reserves the right to not answer any questions deemed unsatisfactory for public viewing.
The BIDDER'S INQUIRIES & RESPONSES will be updated continuously and all attempts will be made to do the final posting by 15:00 on Wednesday prior to the bid opening.
INFORMATION AVAILABLE
 

BID ITEMS
 SPECIALS
PLANS
 PLANHOLDERS




ORDERING PROJECT PLANS AND SPECIFICATIONS

ADDENDUM


 
 
 
 

BIDDER'S INQUIRY SUBMITTAL FORM


Inquiry No.
Inquiry
    1 

  Q:07/15/08
   R:07/18/08

Plan Sheet / Specification Reference= Notice to Contractors Page 1
No prebid meeting is scheduled for this project. 

Question= Do to some items in the scope of this project, it would be very helpful to get inside the building to quantify and gauge some of the tasks.  Can we set up a time and date to have access to the building and building site?

  • The District building is scheduled to be open to review by all potential bidders on the following days and time:

07/23/2008 from 2:00 PM to 3:00 PM
07/30/2008 from 2:00 PM to 3:00 PM
 

Please call (619) 688-6635, with any question regarding the above.

    2 

  Q:07/22/08
   R:07/29/08

Plan Sheet / Specification Reference=  A-301, North & South Elevation, Keynote #1

Question= Plan says; Existing clay tile roof to remain – inspect, patch and repair as necessary.   This is a very open ended requirement and there’s no way of knowing what the extent of the work is without climbing up on the roof and inspecting it. Does your insurance cover this for all the people that are bidding this job?  From the ground, the roof tiles appear to be okay, is there any work that we should include that is not visible from the ground? Also, the roof tiles appear to be very old, and an unusual size. If repairing is needed what tile should we use for as a basis for bidding? (I doubt this size is available at all).

  • The area of the roof to be patched and repaired is after the removal of the vent pipe shown on A-301 Note 22 and the 2" waste down and vent up shown on P2.1 Note 1.

    3 

  Q:07/22/08
   R:07/29/08

Plan Sheet / Specification Reference= All pages/All

Question= The plans I purchased are not a true half size set of plans, and there is a huge lack of dimensions on every page. For example, sheet A-004, A-121, neither of these pages gives the size of the area that the pavers are being re-set We need either a true half size set of plans so that we can scale the dimensions or a plan that shows every dimension of the work. 

  • The true scale shown on the plan sheet border, bottom center, can be used to scale the extent of the pavers to be reset.

   

  Q:07/23/08
   R:07/29/08

Plan Sheet / Specification Reference= 

Question= 1.    The Lead Paint Survey provided by JMR Environmental Services, Inc. identified various components (i.e. cabinets, doors/frames, windows/frames, trim, etc.) which tested positive for lead based paint. The majority of the listed components are scheduled to be demolished as part of this project. However, there appears to be three exterior doors which are to be removed and salvaged for re-use.
 
QUESTION: Is the intent of the project to remove only loose and flaky lead based paint on components scheduled for demolition? What is the extent of full removal (stripping paint to bare substrate) since this building is of historical significance?

  • See the General Conditions and Special Provisions, Section 2.05, Lead Related Construction Work.
     
    2.    Some lead based components will not be demolished as part of this project.
     
    QUESTION: Should the lead based components remaining, be stabilized (loose and flaky paint removal) or should they be completely stripped? Can the items be catergorized by loose and flaky vice stripping abatement activities?
  • See sheet A-102, Key Note 10, and the General Conditions and Special Provisions, Section 2.05, Lead Related Construction Work.
     
    3.    Since this building is classified as “historic”, can an inventory of those items/components deemed historic be provided?
     Your assistance in clarifying this matter is greatly appreciated.
  • The plans and Special Provisions indicate which items/components are historic and are to be refurbished or preserved.  Bid it per the contract documents.

   

  Q:07/24/08
   R:07/29/08

Plan Sheet / Specification Reference= A-601, 11/A-601  

Question= Detail shows pavers as stacked 6” high where note says “Pavers Beyond”. What is this suppose to be? Are these pavers stacked like this?

  • The pavers are not stacked.  The detail is showing the pavers as they slope up towards the concrete topping slab (A-121, note 9).  See A-121, A-201, Section 2, and A-601 detail 7.

   

  Q:07/24/08
   R:07/29/08

Plan Sheet / Specification Reference= A-121 & A-601, A-121 keynote # 9, and 11/A-601    

Question= What is the “concrete topping slab”; thickness, color, finish and spec would be helpful. 

  • Color and finish per sheet A-121, note 9.  Thickness is 3 ½" flush with interior finished floor elevation and sloped as stated on A-121, Note 9.  See the General Conditions and Special Provisions, Division 3 Concrete and Reinforcement.

   

  Q:07/24/08
   R:07/29/08

Plan Sheet / Specification Reference= Keynote # 30  

Question= Note says “patch and repair concrete, match existing texture and color”. Please advise, what the existing is? This comment is repeated throughout these plans, it’s not possible to visit the site and expect to review every one of these “existing conditions” during a short scheduled appointment. Please explain exactly what we are matching, without saying match existing.

  • Please bid per the current contract documents.

   

  Q:07/24/08
   R:07/29/08

Plan Sheet / Specification Reference=  Permits and Licenses, Page 31 Sub-Heading Paragraph No.    5-1.01N, “contractor shall procure all permits…”  “The enviromental quality act may be applicable..” 

Question= 1     We assume since this is a State building that there aren’t any local building permits required? 

  • A building permit from the City of San Diego will not be required.

2     Public Resource Code Section 21000 – 21176; Which part of this code “may be” applicable, as stated. I’ve read some of the code and I don’t understand what would be applied to this project, and where the cost would be?

  • The reference to Public Resource Code is standard contract language in all Department contracts.  For this contract it is likely all environmental requirements were addressed in the environmental document and the contract special provisions.

   

  Q:07/24/08
   R:07/29/08

Plan Sheet / Specification Reference=  10 & 15  of 57, A-121,  6/A-401  

Question= What are the dimensions for the Mobil Shelving system, the overall area where the system is going.  

  • The Mobile Storage System (MSS) is to fit as shown on A-121.  Refer to A-005 for dimension of existing wall to be behind the MSS. 

   
10 

  Q:07/24/08
   R:07/29/08

Plan Sheet / Specification Reference=  DIV 1, Temporary Facilities                                

Question= Is there a requirement for the General Contractor to provide a construction trailer, or office requirements for the inspector? 

  • No.
 
   
11 

  Q:07/24/08
   R:07/29/08

Plan Sheet / Specification Reference=  10, 15, 16, 18 of 57, A-121,  A-401, A-402, A404; Display Cases, Page 184                                    

Question= Display cases details shown on A-404 are not consistent with the elevation drawings. The configurations are different than the detailed elevation on A-404. I checked with www.displaycasedepot.com and they have a multitude of different display cases. Please provide the model and number of the cases that apply to this project.

  • Please bid per the current contract documents.
      
12 

  Q:07/25/08
   R:07/29/08



Plan Sheet / Specification Reference= 12 of 57 Specific Location (plan, elevation, section, etc.) A-201,  keynote # 27 Rigid Insulation Page No.  137

Question= Where exactly is the rigid insulation suppose to go? The arrow reference looks like it points to the center of the rafter bay, but that wouldn’t be a normal installation?

  • Please bid per the current contract documents.

13 

  Q:07/29/08
   R:08/05/08

Plan Sheet / Specification Reference= EE007

Question= Electrical plan show  HP-1 & HP-2 and FC-1 & FC-2 FC units. Mechanical plan shows 3 each units.

  • Mechanical components/work should be bid as shown on the mechanical plans and specifications.  Electrical work should be bid as shown on electrical plans and specifications.
14 

  Q:07/29/08
   R:08/05/08

Plan Sheet / Specification Reference= A-201 3/A-201, keynote # 27

Question= Your response to Bidders inquiry # 12 is not helpful. There is not enough adequate information provided to develop a bid price for this. The documents do not provide a clear understanding of the work. If we have missed something than please simply tell us what we missed? Otherwise; where is the rigid insulation installed, or is the requirement an error?

  • Please bid per the current contract documents.
15 

  Q:07/25/08
   R:08/05/08

Plan Sheet / Specification Reference= Plan Sheet No. 10, 15, 16, 18   A-121,  keynote # 8 Display Cases

Question= What is the “Display  wall” called out on keynote # 8. Provide detail and elevation if this is something we need to include in the bid.

  • Display wall is not a special feature and no additional information is needed.
16 

  Q:07/30/08
  R:08/05/08

Plan Sheet / Specification Reference= A-401, 402, 404            

Question= Re: Bidders inquiry # 11 response: The response does not adequately answer the question. What is the model number and make of the display cases? Contract documents do not have enough information to bid this.

  • The Manufacturers listed in the special provisions are for reference only.  They are not intended to indicate a preference for a particular Brand or Model number.  Display cases shall be manufactured and installed as per the current contract documents.
17 

  Q:08/01/08
  R:08/04/08

Plan Sheet / Specification Reference= Addenda # 2, Page No. 1  Wage Rates                                 

Question= I’m not clear on which wage rate determination applies to this job; Page 2 of the contract documents refers to the California Department of Industrial Relations for determination, which means it’s State Prevailing Wage Rates.  Addenda # 2 refers to a “revision to the Federal minimum wage rates” which is different than State. Page 2 of the “Notice to Contractors” has not been modified, therefore this is a conflict.. 

  •  Because Contract 11-264804 is a federal-aid project, either federal or state prevailing wage rates may apply. When there is a difference between the Federal prevailing wage rate and the State prevailing wage rate determined for similar classifications of labor, the contractor and subcontractors shall pay the higher of the two wage rates.

The Director of the Department of Industrial Relations determines State prevailing wage rates, which can be obtained by accessing the Department of Industrial Relations website at http://www.dir.ca.gov. Also find the predetermined increases applicable to each craft/classification. Click on the subheading of Statistics and Research, then General Prevailing Wage Determinations Menu (Journeyman). Finally, look for the location by county and/or region.

The Federal prevailing wage rates for this project are predetermined by the United States Secretary of Labor and are available through the US Department of Labor’s website at http://www.access.gpo.gov/davisbacon/ca.html Obtain federal wage rates that are in effect within ten (10) days of bid opening.

                                                                     

18 

  Q:08/04/08
  R:08/05/08

Plan Sheet / Specification Reference= 10 of 57 A-121,  10-05, pages 196-201,  Mobile Storage System          

Question= The specification under 10-05 and scaled plans (pg A-121) do not match.  Shelving size in spec is called out at 18”d, while plan A-121 shows scaled size at 12”d.  Also, shelving elevation is not clear (6levels at 13.5” centers will not fit in the specified height restriction).  Specification of ¾” shelving recess in carriage design is proprietary.  Can a clarification be provided on what shelving sizes are required?

  • Mobile Storage System is to be sized as specified in the Special Provisions.  A total of 6 shelves including the bottom will fit within the specified height.  Please bid per current contract documents.

19 

  Q:08/05/08
  R:08/05/08

Plan Sheet / Specification Reference= Project 11-264804       

Question= Duty Senior, Dist 11, got some questions for you. On plans, security sytem, card access & communications request only conduit & pull ropes. Does this mean these systems are being done in-house or are they out for bid? Should they be included in my bid to you?

  • The security system will be installed by the State.  Only those items shown in the current contract documents are to be included in the bid.  Please bid per the current contract documents.

20 

  Q:08/06/08
  R:08/06/08

Plan Sheet / Specification Reference=

Question=Will the State be doing the communication wiring on this project? Is the card access system being installed by the State?

  • Please see response to Bidder Inquiry #19.