Inquiry #1: Can you please post cross-sections for this project?

Inquiry submitted 11/27/2012

Response #1:Submitted for consideration.
Response posted 11/28/2012


Response #2:You can download the cross sections below:


www.dot.ca.gov/dist4/construction/contracts/04-2A4404/XSections.pdf (pdf, 55MB)
Response posted 11/30/2012




Inquiry #2: On sheet 12 L-6, the plans show the structural section from "L" line Sta 248+10 to 253+00 for Rte 152 being structural section 2 and the Private driveway from Sta. 248+60.11 to 253+50.96 is shown to have structural section 3. However on sheets 5-6 (X-4 and X-5) Rte 152 is structural section 3 and the Private Driveway is structural section 4. Can you please clarify the correct structural section for these two areas?
Inquiry submitted 11/29/2012

Response #1:Submitted for consideration.
Response posted 11/30/2012


Response #2:Please refer to Sheets 5-6 (Typical Cross Sections X-4 and X-5) for the correct structural section.

Response posted 12/03/2012




Inquiry #3: Sheet 20 (C-1), there is a detail showing paving conform only at Sta 220+00 to 220+50 and Sta 277+00 to 277+50. Should there also be a paving conform at Sta 101+50 and Sta 117+50? Please clarify.
Inquiry submitted 11/30/2012

Response #1:Submitted for consideration.
Response posted 12/03/2012


Response #2:There will be a paving conform at Sta 101+50 and Sta 117+50.
Response posted 12/04/2012




Inquiry #4: Can Caltrans please post the CAD files for the cross sections? The PDF copies are of poor quality for take-off purposes.
Inquiry submitted 12/04/2012

Response #1:Submitted for consideration.
Response posted 12/04/2012


Response #2:You can download the Microstation files below:

www.dot.ca.gov/dist4/construction/contracts/04-2A4404/XSections_cad.dgn (Microstation file, 11MB)
Response posted 12/06/2012




Inquiry #5: Can you clarify what material is being placed in the Cold Plane AC Pavement Areas? On Q-1 (Sheet No. 106) the quantity for removal is shown but there is no quantity in the Pavement Structure Quantity Table representing replacing the .25' AC (Max) Removal.
Inquiry submitted 12/04/2012

Response #1:Submitted for consideration.
Response posted 12/05/2012


Response #2:Place HMA (Type A). An addendum has been requested to address this question.
Response posted 12/06/2012




Inquiry #6: New Standard Plan NSP T3A note 1 states when Type K railing is less than 2' from edge of traveled way, it needs to be doweled. Section A-A, B-B, C-C, D-D, E-E, and F-F in the staging plans shows the construction area being .5' from the k-rail but not being doweled. Can you clarify if the temporary k-rail needs to be doweled?
Inquiry submitted 12/17/2012

Response #1:Submitted for consideration.
Response posted 12/18/2012


Response #2:The Temporary K-rail needs to be doweled. Please follow NSP T3A Note 1 instructions.
Response posted 12/20/2012




Inquiry #7: Per addendum #1, we are now to include 250 wkg days for plant establishment Type 2.

Since this is an A+B project, Is the amount of time bid, to be inclusive of plant establishment?

Inquiry submitted 12/17/2012

Response #1:Submitted for consideration.
Response posted 12/18/2012


Response #2:The amount of time bid is not inclusive of plant establishment days. Please follow the instruction on page 1 of Notice to Bidders.
Response posted 12/20/2012




Inquiry #8: Is this job still an A + B Job ?
Revised bid item sheet 8A seems confusing.

Inquiry submitted 12/19/2012

Response #1:Submitted for consideration.
Response posted 12/20/2012


Response #2:This is an A+B project. An addendum has been requested to address this question
Response posted 12/21/2012




Inquiry #9: Level 2 project without an Active Treatment System bid item; please explain how the Contractor is to handle / treat water that could be "dirt" as it leaves the site?


Inquiry submitted 12/19/2012

Response #1:Submitted for consideration.
Response posted 12/20/2012


Response #2:Based on the soil condition at the project site, no Active Treatment System is recommended.
Response posted 12/21/2012




Inquiry #10: Follow-up to question #9 - the State is indicating that there is no recommendation for an Active Treatment System. Our QSD (based on review of the plans and knowledge of the area) is recommending a system due to the existing terrain and amount of potential rain water coming onto the site. Along with Water Pollution Control Quantities (WPCQ) (plan sheet WPCQ-1, sheet 22) being slight regarding amount of BMP that are being designed.

Since the States design team and the (potential) project QSD have different opinions regarding the potential risk We now have a follow up question: Who pays for the additional work on a Level 2 project? Our take is this is the State responsibility….. Please review the WPCQ and beef up the design to allow the potential rick can be addressed….


Inquiry submitted 12/21/2012

Response #1:Submitted for consideration.
Response posted 12/21/2012


Response #2:The scope of the project is covered by the Plans, Special Provisions and various Bid Items that have been stipulated. For payment regarding extra work, please refer to Section 5-1.07 of the Special Provisions and Section 9-1.03 of the Standard Specifications.
Response posted 12/31/2012




Inquiry #11: Bid Item 23: Can the State please change this item to the “350 absorb crash cushion” type in lieu of the modules?


Inquiry submitted 12/21/2012

Response #1:Submitted for consideration.
Response posted 12/21/2012


Response #2:Please bid in accordance with the contract plans and specifications.
Response posted 12/31/2012




Inquiry #12: Section 5-1.11 states that the contractor is to install exclusion devices prior to February 1st to prevent migratory birds from nesting at the contractor's expense. Since it will not be possible to accomplish this, will the State be installing the exclusion netting? If not, will the contractor be given time extensions if migratory birds do nest and affect the schedule? If Caltrans is installing the devices, please provide details of what the State is installing so we can price the maintenance if the maintenance will be the contractor's responsibility. Also, who pays for the biological monitoring mentioned in this section?
Inquiry submitted 12/27/2012

Response #1:Submitted for consideration.
Response posted 12/31/2012


Response #2:Caltrans will install exclusion netting before construction starts. Contractor maintains exclusion netting. Caltrans provides the Biological Monitoring.
Response posted 01/07/2013




Inquiry #13: Past projects with similar rock conditions at soil nail walls have resulted in yields in excess of 150% of theoretical shotcrete volume. Will Caltrans be assuming any of this overage as this is not a quantity that can be determined at bid time?
Inquiry submitted 12/27/2012

Response #1:Submitted for consideration.
Response posted 12/31/2012


Response #2:No, Caltrans will not be assuming costs of any of the overages that might occur in the shotcrete volume on this project.

Refer to the " Copy of Bid Items List" in the special provisions pages 4 and 5 for shotcrete items. Note that these Items are (F), final pay items. For information on final pay Items reference Section 9-1.015 of the Standard Specifications.

Response posted 01/04/2013




Inquiry #14: Per the quantity sheet Q-1, it appears that the cold plane AC item (#38) does not include the 0'-.08'/0'-.31'(??) thick cold planing for the conforms at the driveways, as shown on C1/C2 (only the .25' for the AC replacement). Is it possible to provide table with qty for each type of driveway? and revise the quantity.
Inquiry submitted 12/28/2012

Response #1:Submitted for consideration.
Response posted 12/31/2012


Response #2:Unless an addendum is issued addressing your concern, please bid per the current contract bid documents.
Response posted 01/07/2013




Inquiry #15: Drainage detail sheet DD-6 shows B3-9 gutter at top of wall with 6" dia WSP/grate inlet and RSP backing #2 --but-- Retaining wall plan R3-1 does not have B3-9 gutter, RSP backing #2 or 6" WSP, but has type 60 barrier & weep holes Which is correct?
Inquiry submitted 12/28/2012

Response #1:Submitted for consideration.
Response posted 12/31/2012


Response #2:R3-1 is correct. RSP Backing No. 2 (Method B) will be relocated at the end of the retaining wall and concrete barrier.
Response posted 01/07/2013




Inquiry #16: Addendum one is indicating sheet nine of the bid item list is to be replaced. Sheet nine is the subcontractor listing in the bid book. Please correct promply?
Inquiry submitted 01/09/2013

Response #1:Submitted for consideration.
Response posted 01/10/2013


Response #2:See Addendum 4.
Response posted 01/14/2013






The information provided in the responses to bidder inquiries is not a waiver of Section 2-1.03, “Examination of Plans, Specifications, Contract, and Site of Work,” of the Standard Specifications or any other provision of the contract, nor to excuse the contractor from full compliance with the contract. Bidders are cautioned that subsequent responses or contract addenda may change a previous response.