Inquiry #1: Can you please post environmental permits and biological reports associated with this project? We would like to review them so we can see the background regarding the PLACs, as well as the biologist requirements. Thank you!
Inquiry submitted 05/08/2017

Response #1:Please note 2015 Standard Specifications, Section 14-6 Biological Resources. Bid per current contract documents.
Response posted 05/09/2017




Inquiry #2: Will "Duct Plowing" be an acceptable installation method for the innerduct?
Inquiry submitted 05/09/2017

Response #1:: "Duct Plowing" will not be an allowed method.


Response posted 05/09/2017




Inquiry #3: REFER TO CONTRACT OR SECTION 9-1.11C OF THE SPECIAL PROVISIONS AMENDMENTS AS IT STATES IN PART, "5. Overhead costs incurred by your subcontractors of any tier or suppliers" ARE EXCLUDED FROM THE BID PARTICIPATION IN THE TRO BID ITEM. HOW WILL THE STATE COMPENSATE WHEN A SUBCONTRACTOR REQUEST ADDITIONAL COMPENSATION IN THE EVENT OF A CONTRACT TIME EXTENSION WHO HAS NOT RECEIVED FULL AND PROPER COMPENSATION?
Inquiry submitted 05/23/2017

Response #1:submitted for consideration
Response posted 05/23/2017


Response #2:Please see Standard Specifications 2015, Section 1-1.07 Definitions, page 8, Contractor. See Section 5 Control of Work, 5-1.13 Subcontracting, and Section 9-1.11C Payment Inclusions which does not include overhead costs incurred by the subcontractors.
Response posted 05/23/2017




Inquiry #4: REFER TO SECTION 9-1.16C. IT IS TYPICAL FOR THE FIBER OPTIC EQUIPMENT AND CABINETS TO BE PART OF THIS SECTION AND ELIGIBLE FOR PROGRESS PAYMENTS. PLEASE CONFIRM IF THAT CAN BE PART OF THE LIST OF ITEMS.
Inquiry submitted 05/23/2017

Response #1:submitted for consideration
Response posted 05/23/2017


Response #2:Your concern has been investigated. An addendum will be forthcoming.
Response posted 05/23/2017




Inquiry #5: On ED-41, Modify WVDS-(Solar), Note 2 under the Legend states: See Sheets E-226 and E-227 for Equipment Modifications inside the cabinet. However, I cannot find Sheets E-226 and E-227 in the plans. Please identify where these sheets can be found.

On ED-44, Modify WVDS-AC Power (Removal), Note 2 under the Notes states: See Sheets E-229 and E-230 for Equipment Modifications inside cabinet. However, I cannot find Sheets E-229 and E-230 in the plans. Please identify where these sheets can be found.

Inquiry submitted 05/25/2017

Response #1:submitted for consideration
Response posted 05/25/2017


Response #2:Inquiry #5 has been addressed under Addendum #2.
Response posted 06/08/2017




Inquiry #6: Will Caltrans District 8 consider Trafficware's WVDS an equivalent alternate to the Sensys WVDS called out in Section 86-2.2.1B(1)General of the Special Provisions, for the purpose of bidding this project?
Inquiry submitted 05/25/2017

Response #1:submitted for consideration
Response posted 05/25/2017


Response #2:Please bid per current contract documents.
Response posted 06/05/2017


Response #3:Please see Addendum No. 2.
Response posted 06/06/2017




Inquiry #7: Reference: Special Provisions, Section 86-2.21B(1) General

The reference section specifies that VSN components must be manufactured by Sensys Networks. Will Caltrans District 8 consider VSN and WVDS components manufactured by Trafficware to be equal substitutes for the purpose of bidding this project?

Inquiry submitted 05/25/2017

Response #1:submitted for consideration
Response posted 05/25/2017


Response #2:Please bid per current contract documents.
Response posted 06/05/2017




Inquiry #8: Please clarify if tamper resistant cover’s for pull boxes are required for this project. If so, please clarify how the contractor is to interpret which box is being used with tamper resistant covers over non tamper resistant covers.

Inquiry submitted 05/25/2017

Response #1:submitted for consideration
Response posted 06/05/2017


Response #2:Please see Addendum No. 2.
Response posted 06/06/2017




Inquiry #9: THE LEVEL SURFACE F/O INSTALLATION IS IS SHOWN AT VARYING DISTANCES FROM THE EP. WHAT IS THE EXPECTED RANGE OF DISTANCE FROM THE EP IS THE 'TRENCH IN DIRT' EXPECTED TO BE INSTALLED AT? ARE THERE ANY OTHER TRENCH DETAILS TO CONSIDER IN THE BID?
Inquiry submitted 05/30/2017

Response #1:No specific distance. The conduit installation must meet the 2015 Standard Plans, Specifications, and special provisions. The intent is to keep the fiber optic Splice Vaults out of the natural flow lines to keep mud and debris out. Please bid per current contract documents.
Response posted 06/05/2017




Inquiry #10: PLEASE CONFIRM SECTION 86-1.02C(4) AND SUBSECTIONS ARE NOT USED IN THIS CONTRACT. IF IT IS, PLEASE CLARIFY WHERE.
Inquiry submitted 05/30/2017

Response #1: With regard to 86-1.02C(4) : Your concern will be addressed on forthcoming addendum.
Response posted 06/05/2017


Response #2:Please see Addendum No. 2.
Response posted 06/06/2017




Inquiry #11: WHAT CURRENT ETHERNET AND SWITCH EQUIPMENT MAKE AND MODELS ARE ACCEPTABLE OR ARE CURRENTLY IN USE TO CONSIDER FOR THE NEW PURCHASE AND INSTALLATION ON THIS PROJECT WHICH ARE COMPATIBLE WITH THE DISTRICT FIBER SYSTEMS.
Inquiry submitted 05/30/2017

Response #1:The recommended manufacturers for the Ethernet equipment are:

-SIEMENS ( Ruggedcom and SCANLACE models)
- MOXA networking products
-HIRSCHMAN Ethernet products

Response posted 06/05/2017




Inquiry #12: The electrical system plan detail, detail for all electrical systems, plan sheet 450 conflicts with the backfill requirements in the special provisions. Which shall prevail?
Inquiry submitted 06/05/2017

Response #1:submitted for consideration
Response posted 06/05/2017


Response #2:: Plan Sheet page 450 is only for Direct Buried Innerduct that contains fiber optic cable.
Response posted 06/05/2017




Inquiry #13: Due to the length and closure restrictions and testing, can the duration of the project be extended an additional 40 more working days?
Inquiry submitted 06/05/2017

Response #1:submitted for consideration
Response posted 06/05/2017


Response #2:Please bid per current contract documents.
Response posted 06/05/2017




Inquiry #14: Caltrans has issued pricing for VSN modules in section 86-2.12B(1)up a valid date of December 31, 2016. Please verify that the pricing has been extended for the duration of the project time.
Inquiry submitted 06/05/2017

Response #1:submitted for consideration
Response posted 06/05/2017


Response #2:The price was extended to December 31,2017.
Response posted 06/05/2017




Inquiry #15: Plan Sheet 450 show a leveled surface installation in 'dirt' and in 'A/C' but there are some trench details missing. Please clarify the separation between innerducts, separation between the innerduct and trench walls, and the separation between the trench walls and power/other conduit(s).

Will there be any other types of trench details provided for the project to consider? Can you clarify other trench details including the separation requested as above?

Inquiry submitted 06/05/2017

Response #1:submitted for consideration
Response posted 06/05/2017


Response #2:There is no separation requirement for the innerducts as long as they are embedded in the sand as shown.

The power conduits must meet the minimum depth shown and must be outside of the sand bedding.

There is no requirement for the distance between the conduits/innerducts and the trench wall.

No other trenching details will be provided.

Response posted 06/06/2017




Inquiry #16: Addendum 2 issued a revised materials information handout. Is the bidder to assume the geotechnical baseline information provided is for this 'TMS' project and not for the 'CMS' project as noted in that report? This project is for the field TMS installations not just the CMS.
Inquiry submitted 06/05/2017

Response #1:submitted for consideration
Response posted 06/05/2017


Response #2:The Geotechnical information is only for the installation of the CMS signs.
Response posted 06/05/2017




Inquiry #17: Section 6-2.03 of the special provisions list materials to be department furnished. Please confirm that when either or both the plans and project specifications also list other department furnished materials and are not noted in the Section 6-2.03, they will be furnished by the department (i.e.: CMS Harness Cable) to the contractor. Please clarify if otherwise.
Inquiry submitted 06/05/2017

Response #1:submitted for consideration
Response posted 06/05/2017


Response #2: The CMS Harnesses and CMS Cabinet are included with the Department-Furnished CMS Sign System.
Response posted 06/06/2017




Inquiry #18: Refer to addendum #2 plans sheet 253. Please confirm Construction Note #1 at the N/B entrance ramp is in not to be used.
Inquiry submitted 06/05/2017

Response #1:Correct. Construction Note #1 at the Northbound Entrance ramp pointing to existing conduits does not apply to Construction Note #1 on Sheet E-1.
Response posted 06/06/2017




Inquiry #19: The quantities on the EQ drawings EQ 2,4,6,8,10 are inconsistent and/or different than the quantities shown on the modify electrical system drawings E-153 and E-154.
Please confirm which pages have the correct quantity of VSN system units for bidding purposes.

Inquiry submitted 06/07/2017

Response #1:submitted for consideration
Response posted 06/07/2017


Response #2:Please bid per contract documents.
Response posted 06/08/2017




Inquiry #20: We would like to request an extension of bid submittal time to incorporate the changes and allow plan holders to prepare a fair and competitive proposal.

Do to the recent changes & short time frame included with addendums 2 & 3.
We'd also like to point out that "request for clarification #5" has not been answered yet.

Inquiry submitted 06/07/2017

Response #1:submitted for consideration
Response posted 06/07/2017


Response #2:Your concerns have been addressed under Addendum #2. Bid per contract documents.
Response posted 06/08/2017




Inquiry #21: The amount of questions including Question No. 5 (Unanswered) and addendums issued has not allowed sufficient time to incorporate the changes with our vendors and subcontractors. We would like to request an extension to the bid due date to insure that all clarifications and changes are reviewed appropriately.
Inquiry submitted 06/07/2017

Response #1:Bid per contract documents.
Response posted 06/08/2017






The information provided in the responses to bidder inquiries is not a waiver of Section 2-1.07, “JOB SITE AND DOCUMENT EXAMINATION” of the Standard Specifications or any other provision of the contract, nor to excuse the contractor from full compliance with the contract. Bidders are cautioned that subsequent responses or contract addenda may change a previous response.