SHA-044-34.7 Upgrade lighting at Shingletown SRRA
Bidder Inquiry / Response
4/25/14
Inquiry:

[1] Is 2” conduit with 3 #1 conductor existing or new? If new, how long is conduit run? Are conductors per utility or Caltrans specifications? This is concerning the service conduit.

[2] There are no details on plans that show what type of construction area signs or how many?


4/29/14
Response: 4/29/14: [1] Existing
[2] There are no construction area signs for this project. The rest area will be closed.


4/28/14
Inquiry:

Are you going to require welding inspection & associated fees for this contract - it is not addressed.

Time is running out. This bid has to be Fed-exd tomorrow! These questions need to be addressed or we can't get pricing.


4/29/14

 

 

4/29/14

Response: Your inquiry is under review. Please note that due to the current time frame between the inquiry submittal and the bid opening date, a response may not be provided before the bid opening. If a response is not provided before the bid opening addressing your concern, please bid per the current contract documents. Thank you for your patience.

Please refer to Section 11-3 of the Revised Standard Specifications (starting on page 83 of 287) and Section 11-3 of the 2010 Standard Specifications.



'
Inquiry:

'
Response:


'
Inquiry:

'
Response:


'
Inquiry:

'
Response:


  The responses to bidder's inquiries, unless incorporated into a formal addendem to the contract, are not a part of the contract and are provided for the bidder's convenience only. In some instances, the question and answer may represent a summary of the matters discussed rather than a word-for-word recitation. The availability or use of information provided in the responses to bidder's inquiries is not to be construed in any way as a waiver of the provisions of Section 2-1.03 of the Standard Specifications or any other provision of the contract, the plans, Standard Specifications or Special Provisions, nor to excuse the contractor from full compliance with those contract requirements. Bidders are cautioned that subsequent responses or contract addenda may affect or vary a response previously given.