| CONTRACT NO: | 11-2T0894 |
| ROUTE / KP | 11-SD-15-M43.9 |
| LOCATION | In San Diego County In Escondido At North County Fair Overcrossing |
| DESCRIPTION | Construct Barrier Transfer Machine Facility. |
| ESTIMATE | $ 5,300,000 |
| WORKING
DAYS |
565 |
| ADVERTISE DATE | 06/02/2008 |
| BID OPENING | 07/24/2008 |
| FINAL POSTING |
07/23/08
@ 1600 |
The Caltrans District
11
Office is located at 4050 Taylor Street, San Diego, CA 92110. The
District 11
Duty
Senior telephone number is (619) 688-6635. Please submit all inquiries
in the proper format by fax to (619) 688-6988 or e-mail to:
Duty_Senior_Const_District11@dot.ca.gov.
The responses to
bidder' inquiries, unless incorporated into a formal addenda to the
contract,
are not a part of the contract and are provided for the bidder's
convenience
only. In some instances, the question and answer may represent a
summary
of the matters discussed rather than a word-for-word recitation. The
responses
may be considered along with all other information furnished to
prospective
bidders for the purpose of bidding on the project. The availability or
use of information provided in the responses to bidder' inquiries is
not
to be construed in any way as a waiver of the provisions of Section
2-1.03
of the Standard Specifications or any other provision of the contract,
the plans, Standard Specifications or Special Provisions, nor to excuse
the contractor from full compliance with those contract requirements.
Bidders
are cautioned that subsequent responses or contract addenda may affect
or vary a response previously given.
Caltrans District 11 Construction
Department
has developed this method of answering Bidder's Inquiries to better
serve
the needs of the Contractors who bid on our Projects. Caltrans District
11 Construction Department will post all of the questions submitted by
any of the contractors that are registered Planholders for that
Contract,
but reserves the right to not answer any questions deemed
unsatisfactory
for public viewing.
The BIDDER'S
INQUIRIES
& RESPONSES will be updated continuously and all attempts will be
made
to do the final posting by 15:00 on Wednesday prior to the bid opening.
INFORMATION
AVAILABLE
|
|
|
|
|
|
|
|
ORDERING
PROJECT PLANS AND SPECIFICATIONS
ADDENDUM
|
|
|
BIDDER'S INQUIRY SUBMITTAL FORM
|
|
Inquiry |
|
1
Q:06/17/08 |
Plan Sheet / Specification
Reference= Please clrify the location of the concrete deadman: Building Section A on Sheet ST2-1 Section view A on Sheet ST5-3 Question= Please clrify the location of the concrete deadman: Building Section A on Sheet ST2-1 indicates that the location is 21,950 mm from face of wall "BTM2" on grid line 6 to the centerline of the concrete deadman. Section view A on Sheet ST5-3 indicates the distance is 16,500 mm from the centerline of wall "BTM2" on grid line 6 to the centerline of the concrete deadman.
|
|
2
Q:06/24/08 |
Plan Sheet / Specification
Reference= Section 12-1.04 schedule of values of the says that
bond premium and other such items will not be paid under the various
building items and shall be inlcuded in the mobolization bid item for
the entire project. The bid schedule does not include a bid item for
mobolization.
Question= Where shall the contractor include the cost for bond and other such items?
|
|
3
Q:07/14/08 |
Plan Sheet / Specification
Reference= detail 3 / A5-1
Question= DETAIL CALLS OUT
"MOLDED TRIM". IS THIS TRIM THE SAME AS WHAT THE SPECS SAY
IS "TRIM BAND AT SPLIT FACE CONC. MASONRY: MD 1079" ? ( AND NOT A
PRECAST CONC./OR CMU PRODUCT)
A. WHO SUPPLIES
IT? B. WHO INSTALLS IT ? C.
WHO MANUFACTURES
IT?
D.IT APPEARS THAT THE CMU IS
NOTCHED TO RECEIVE
THIS, AND IT IS ALSO ANCHORED TO THE VERTICAL REBARS WITH SHEET METAL
SCREWS BEING TIDED TO THEM . THIS SEEMS A BIT EXCESSIVE.
|
|
4
Q:07/17/08 |
Plan Sheet / Specification
Reference= Section 12-14 Conveying Systems, 12-14.01 Bridge Crane and
Hoist
Question= Part 1 General
/ Summary / Scope:
|
|
5
Q:07/22/08 |
Plan Sheet / Specification
Reference= 762mm Dia. CIDH concrete piles, sheet No. 143
Question= 1. Spiral
spacing of 115mm (4 1/2" o.c.) does not meet your current Clatrans
design windows for rebar spacing of 5" x 5". Please address and
redesign.
2. Clearance of 50mm
(2") is not propoer ACI for concrete cast
against a dirt face. The clearance you show is for a formed
surface as in a column. This needs to be addressed and changed.
|