BIDDER'S INQUIRIES & RESPONSES
DISTRICT 11 CONSTRUCTION

 
CONTRACT NO: 11-091824
ROUTE / KP 11-SD-905-R13.9/R18.6
LOCATION In San Diego County In San Diego From 0.6 Km East Of Cactus Road To 0.3 Km West Of The Mexico Border.
DESCRIPTION To Construct New Freeway
ESTIMATE $ 79,000,000
WORKING DAYS
905 (Including 250 Working Days of Plant Establishment)
ADVERTISE DATE 10/22/2007
BID OPENING 12/13/2007
FINAL POSTING 12/12/07   @   16:05

BID RESULTS


The Caltrans District 11 Office is located at 4050 Taylor Street, San Diego, CA 92110. The District 11 Duty Senior telephone number is (619) 688-6635. Please submit all inquiries in the proper format by fax to (619) 688-6988 or e-mail to:

Duty_Senior_Const_District11@dot.ca.gov.
The responses to bidder' inquiries, unless incorporated into a formal addenda to the contract, are not a part of the contract and are provided for the bidder's convenience only. In some instances, the question and answer may represent a summary of the matters discussed rather than a word-for-word recitation. The responses may be considered along with all other information furnished to prospective bidders for the purpose of bidding on the project. The availability or use of information provided in the responses to bidder' inquiries is not to be construed in any way as a waiver of the provisions of Section 2-1.03 of the Standard Specifications or any other provision of the contract, the plans, Standard Specifications or Special Provisions, nor to excuse the contractor from full compliance with those contract requirements. Bidders are cautioned that subsequent responses or contract addenda may affect or vary a response previously given.
Caltrans District 11 Construction Department has developed this method of answering Bidder's Inquiries to better serve the needs of the Contractors who bid on our Projects. Caltrans District 11 Construction Department will post all of the questions submitted by any of the contractors that are registered Planholders for that Contract, but reserves the right to not answer any questions deemed unsatisfactory for public viewing.
The BIDDER'S INQUIRIES & RESPONSES will be updated continuously and all attempts will be made to do the final posting by 15:00 on Wednesday prior to the bid opening.
INFORMATION AVAILABLE
 
CROSS SECTIONS
BID ITEMS
 SPECIALS
PLANS
 PLANHOLDERS
CROSS SECTIONS
Last Updated
12/03/07

CROSS SECTIONS
Last Updated
12/05/07
INFORMATION HANDOUTS
Last Updated
12/05/07

ADDENDUM


 
 
 
 

BIDDER'S INQUIRY SUBMITTAL FORM


Inquiry No.
Inquiry
 1

Q:10/29/07
R:10/29/07
Plan Sheet / Specification Reference= Page 130 of the Special Provision Section 2-1.03 Preward Qualification Questionnaire.  

Question= There is no Preward Qualification Questionnaire included in my proposal book, is it going to be required? If so who do we get a copy of it from?

  • An addendum will be issued and the Praward Qualification Questionnaire will be included. 
          
 
2

Q:10/30/07
R:11/15/07

Plan Sheet / Specification Reference=

Question= HOW ABOUT SOME CROSS-SECTIONS!!!
  • Cross sections are available as of 11/15/07 and can be downloaded for printing from the link above at any local printing firm or on your own printing equipment:

     MESA REPROGRAPHICS 
     5560 Ruffin Road Suite 5 
     San Diego, CA 92123 
     (858) 541-1500    FAX (858) 278-0558 
     e-mail to  plot@mesareprographics.com San Diego, CA 92123


3

Q:11/07/07
R:11/15/07
Plan Sheet / Specification Reference= Special Provision Section 5-1.17 Project Information

Question= Special Provision Section 5-1.17 Project Information page 155, states that cross sections are available in electronic copy. When will the cross sections be available and in what format?
  • Cross sections are available in pdf format.

4

Q:11/14/07
R:11/15/07
Plan Sheet / Specification Reference= Special Provisions section 5-1.17.

Question= Due to the fact that cross sections and the additional information as described on page 155 of the Special Provisions are not yet available, we would like to request that the bid date be extended a
minimum of 3 weeks.
  • Cross sections are now available and the bid opening date remains unchanged.

5

Q:11/15/07
R:11/20/07
R:12/05/07
Plan Sheet / Specification Reference= Special Provisions Section 5-1.17 Project Information

Question= Special Provisions Section 5-1.17 Project Information page 155, states that Haul Road Information, Utilities Site Preparation Requirements and Geotechnical Design Report Dated 09-14-2005 are available for inspection at the District Office. Will these be posted also on your website also for our use and when will they be available.
  • The information handouts excluding the Haul Road Information are avaiable as of 11/20/07.
  • Haul Road Information is available as of 12/05/07 at the link listed above.

6

Q:11/15/07
R:11/20/07
Plan Sheet / Specification Reference= Contour grading plans

Question= Can you please make contour grading plans available that show the existing ground on all sheets, and please verify the consitence of design lines across matchlines.
  • These plan sheets can be downloaded for printing from the link above.

7

Q:11/16/07
R:11/20/07
Plan Sheet / Specification Reference=

Question= Where can we find the Materials Information Sheet???
  • Material Design Report is available as of 11/20/07.

8

Q:11/16/07
R:11/30/07
Plan Sheet / Specification Reference= Fiber Optic Communications System for the Construct New Freeway Project #11-09184.  the Electrical drawings E-1 through E12 and E-17, E-18 have a note at the top – “ 1 – Lighting and sign illumination, lighting (city street), and F/O communications system IS PART OF THE PROJECT PLANS PHASE III.”

Question= 1.    What does this mean? “PHASE III” part of project.
2.    What is included as total Fiber Communications System for this project?   Conduit pathway, Fiber Cabling, Connections as a complete operating network. Drawings show pathway and indicate fiber type and count.  Interface equipment is shown / indicated in Camera System areas.
3.    Is this portion of the bid (Fiber Optic Communications System) responsible for complete Fiber Optic Communications design? It obviously ties into the camera system. I do not see a breakout of this in the costing schedule.

  • 1. These plans belong to Phase III as described under "SECTION 1  SPECIFICATIONS AND PLANS" which     states:
Phase III shall consist of the following work:

Pavement Delineation Plans
Sign Plans/Quantities
Sign Detail
Signals, Lighting and Electrical Systems
Complete design of Phase III, including final plans for Phase III, will be provided to the Contractor within 120 days after approval of the contract.
The issuance of Phases II and III shall be by change order in conformance with Section 4, "Scope of Work," of the Standard Specifications.
Project plan sheets marked, "Preliminary for Bidding Purposes Only," shall not be considered complete as to the design.  These plan sheets are provided only to show the scope of the work to be performed, and shall only be used for the purpose of bid preparation.
  • 2. The system includes only what is listed in the Special Provisions under the Cost Breakdown table.
  • 3. The Final phase III plans will show the complete design using the items shown in the cost breakdown table.

9

Q:11/19/07
R:12/10/07

Plan Sheet / Specification Reference= Plan sheet 611 of 895 Airway Road Detour.

Question= The structural section for "AD2" calls for 165 mm DGAC.  What is DGAC and where is paid for? The structural sections also calls for 300 mm Class 5 AS.  Please provide the gradation requirements for the Class 5 AS per section 25-1.02C of the Standard Specifications.

  • Due to the Design Sequensing nature of this project, the DGAC (Dense Graded Asphalt Concrete) will be reflected as AC Type A and class 5 as class 4, in the deliverables. These are reflected in the Special provisions.

10

Q:11/21/07
R:11/30/07
Plan Sheet / Specification Reference= Reference Special Provision Section 10-1.16, pages 225-227, and the Information Handout supplied on 11/20/07 titled "Utilities Site Preparation By the Contractor Requirements"

Question= The Working Days listed in the Special Provisions Section 10-1.16 for the various Utility Companies to complete their work does not match the Working Days listed in the Information Handout for the Utility Companies to complete their work.  Which is correct?
  • Both are correct: (Notification Days for Utility + Working Days for Utility) = Working Days for Contract
  • Please refer to the site preparation requirements in the Infomation Handout "Utilities Site Preparation By the Contractor Requirements".

11

Q:11/21/07
R:11/26/07

Plan Sheet / Specification Reference= Bid Item # 55 Gravel Blanket

Question= There is no mention of gravel blanket in the Specials and I am unable to locate any on the Plan Sheets. Please provide the location of gravel blanket on the plans along with a typical section drawing and a Special Provision section describing the blanket and method of payment.

  • Please refer to page 395, DRAINAGE DETAILS DD-10, of the plans. Method of payment per the bid item #55 is per M3.


12

Q:11/21/07
R:11/27/07
Plan Sheet / Specification Reference= Item 48 Roadway Exc. Plan sheets 69 thru 105. Embankment Profile Plans P1 -P37

Question= Embankment total shown on sheets P1-P37 is 631962 M3. My estimate of the Foundation Treatment shown on sheet 148 is 100,000 M3 for a total Rdwy Exc of 731962 Bid Item 48 is 1,310,000 M3.
Does the Bid Qty for  Item 48 Rdwy Exc include quatities not included on sheets 69-105 plus Foundation Treatment shown on sheet 148? If so where do I find it?
  • Please refer to sheets 676, 686, 694 & 702 for earthwork quantities.  


13

Q:11/27/07
R:11/30/07
Plan Sheet / Specification Reference= Special Provisions Section 3-1.01B, First Paragraph

Question= This section explians that meeting the goal for the DBE particiapation or demonstrating, to the satisfaction of the Department, adequate good faith efforts to do so is a condition of being eligible
for award of contract.  I believe that Caltrans is still under a RACE NEUTRAL bid practice until the Federal Government approves the disparity study.  Does the contractor need to meet the goal or complete a good faith effort to do so?
  • Please refer to Addendum #1 for Specification "3-1.01B  AWARD  AND  EXECUTION OF CONTRACT"


14

Q:11/27/07
R:12/07/07

Plan Sheet / Specification Reference= ITEM 48, ROAD EXC.  SPECIAL PROVISIONS SECTION 10-1.34, paragraph 4, "surplus excavated material shall become the property of the contractor..."

Question= Are the finish grades shown on the plans on what appears to be a "borrow" area at Enrico Fermi and Otay Mesa mandatory?

  • Per the Design Sequencing nature of this project, Please refer to sheet 694 Q23 of the contract plans.


15

Q:11/27/07
R:11/27/07
Plan Sheet / Specification Reference= ITEM 48, ROAD EXC.  There are numerous references to "SELECT" excavation and embankment throughout the plans.

Question= What is the definition of "SELECT" material?
  • The Typicals show "Embankment Select," Note 3 on the Typicals directs to the Construction Details, Construction Detail Sheet C-18 shows Selected Material.
  • Selected Material is per Section 19-2.07 of the Standard Specifications.

16

Q:11/27/07
R:12/05/07
Plan Sheet / Specification Reference= Special Provisions

Question= When will the Haul Road Information be posted for Contractor down loading?
  • Haul Road Information is available as of 12/05/07 at the link listed above.

17

Q:11/28/07
R:12/05/07

Plan Sheet / Specification Reference=

Question= Is the information in Add#1 regarding load limitations for Otay Mesa Road the extent of the Haul Road information?

  • No, there is more information available in the "HAUL ROAD INFORMATION" link, above.


18

Q:11/28/07
R:12/06/07

Plan Sheet / Specification Reference= 176 Sewer Manhole B SS-4 10-4.07

Question=The 1st MH @ or near Sanyo calls for a remove & replace. Does the base need to be replaced?

  • Yes

19

Q:11/30/07
R:12/10/07

Plan Sheet / Specification Reference= Plan Sheet #33 of 895 - Typical Section of line "OTAY1" &
Plan Sheet 28 & 29 - Typical Section of line "LMD"

Question= Line "OTAY1" section shows class 4 material over top of the class 2 material.  This is contrary of the rest of the project.  Is this a mistake or is it the intent to install class 4 material over the class 2 material and then pave on it?  How will your answer affect the quanitity sheets calculated in regards to line "OTAY1"?

  • This is a typo.

    Line "LMD" Section shows all class 2 material under the AC yet the quantity sheet 680 for this line indicated the use of Class 4 material. Please clarify.
  • Please bid per the current contract documents.


20

Q:11/27/07
R:11/30/07
Plan Sheet / Specification Reference= Cross Sections

Question= I could not find Cross Sections for Britannia Road (BRN1).  Can you please make them available?
  • They are posted above under cross sections.


21

Q:11/27/07
R:11/30/07
Plan Sheet / Specification Reference= Cross Sections

Question= I could not find Cross Sections for La Media Road (LMD).  Can
you please make them available?
  • They are posted above under cross sections.
22

Q:11/30/07
R:12/12/07

Plan Sheet / Specification Reference= Plan sheet 472 and 520 of 895.

Question=1.Where is the concrete and rebar for the concrete encasement to be paid for?
2. Where is the Grouting of the Annular space called for on sheet 520 to
be paid for?

  • Please bid per the current contract documents.

 

23

Q:11/30/07
R:12/05/07

Plan Sheet / Specification Reference= Sheet 247 G-12

Question= Can you please provide Existing contours for Sheet G-12 (pg.247).  There are none shown on the plan.

  • Contour lines on the plans that were mailed out are quite faint. Plan sheets printed from the "PLANS" link above, are much more legible.

24

Q:11/30/07
R:12/05/07

Plan Sheet / Specification Reference= Cross Sections

Question= The LMD and BRN1 Cross Sections are not above as stated unless they are under a different name.  Please make them available, or clarify what file they are under.

  • Please click on the third "CROSS SECTIONS" link above.


25

Q:12/03/07
R:12/07/07

Plan Sheet / Specification Reference= Plan sheet 257 shows an embankment to be constructed labeled "A3".  Plan sheet 694 under "EARTHWORK QUANTITIES" lists "A3" as having a requirement of 350,000 M3 of "SELECT MATERIAL". Based on a site visit, it appears that there is a large embankment in existence at this time that closely resembles the mew embankment to be constructed shown on the plans.

Question= Is there an additional embankment to be constructed requiring 350,000 M3 of "SELECT MATERIAL", or is all or part of the planned embankment already in existence, with the resultant serious impact on the potential for surplus material, which is the contractors' responsibility according to the specifications.

  • The proposed 350,000 M3 refered to on page 694 of the plans is for the construction of "A3" as shown on page 257.


26

Q:12/03/07
R:12/07/07

Plan Sheet / Specification Reference= SECTION 10-1.32 "CLEARING AND GRUBBING", paragraph 10, states: "Vegetable growth from clearing and grubbing operations may be disposed of in embankments in conformance with the provisions in "EARTHWORK" of these special provisions. SECTION 10-1.34 "EARTHWORK" is silent in this regard

Question= Under what conditions and constraints may "vegetable growth from clearing and grubbing operations may be disposed of in embankments..."

  • Post award and approval of the contract, a no cost change order will be issued to eliminate the "Vegetable growth from clearing and grubbing operations may be disposed of in embankments in conformance with the provisions in "EARTHWORK" clause from SECTION 10-1.32 "CLEARING AND GRUBBING", of the Special Provisions for this contract. Therefore, disposal of vegetations in the embankment will not be allowed.




27

Q:12/03/07
R:12/07/07

Plan Sheet / Specification Reference= Item# 89(F)Structural Concrete, Bridge, Plan Sheets 543,544,566, 569, Special Provision page 230

Question= Per section 10-1.20, page 230 of the special provisions, La Media UC requires two 15.9 meter False-work roadway openings and one 1.52 meter pedestrian opening during construction. However, per the construction staging plans, pages 543 and 544, construction of NB La Media will occur during stage 1. Upon the completion of stage 1, stage 2 requires the construction of SB La Media Blvd, the relocation of all roadway utilities and the construction of La Media UC simultaneously. It is also indicated on page 566 that there will be a two lanes and one shoulder opening in stage 2 and page 569 shows the South Bound lane of La Media closed during stage 2a. At no time will there be the required 15.9 meters of roadway in both directions to accommodate the required False-work openings. Please review this information and provide the suitable False-work openings for the correct staging of the La Media UC.

  • In accordance to Section 5-1.04 of the Standard Specifications, Special Provisions govern over the plans. Please bid per the current contract documents.


28

Q:12/04/07
R:12/07/07

Plan Sheet / Specification Reference= 175, 15" Sewer

Question= When bypassing the sewer on Airway to Harvest, the plans want the MH R&R'd. Does the base need to be removed?

  • Yes.

Since the ie is not changing the base could stay. If the base is removed, bypassing becomes a problem.


29

Q:12/04/07
R:12/05/07
Plan Sheet / Specification Reference= Special Provisions Section 10-1.42 Aggregate Subase and Section 10-1.43 Aggregate Base

Question= In past projects it has been Caltrans preference to allow the use of 100% RECYCLE Class 4 Aggregate Subbase and 100% RECYCLE Class 2 Aggregate Base.  This was accomplished by adding language to the special provisions to change the wording in the Standard Specifications Section
25 and 26, respectively, that only allows 50% RECYCLE product to be used.  Please review and clarify if the intent of the specification is to require the use of at least 50% virgin aggregate.

  • Please refer to Section 25, "AGGREGATE SUBBASES", and Section 26, "AGGREGATE BASE",  of the AMENDMENTS TO JULY 1999 STANDARD SPECIFICATIONS in the Special Provisions.


30

Q:12/06/07
R:12/07/07

Plan Sheet / Specification Reference= Question #1 - Bid Item #135.

Question= Question #1 - Does this pay for RCP sewer pipe encasement per plan sheet # 465, if not where is this paid?

  • Yes


31

Q:12/06/07
R:12/07/07

Plan Sheet / Specification Reference= bid item #145

Question= Does this pay for WSP encasement per plan sheet #466-468, if not where is it paid?

  • Yes



32

Q:12/06/07
R:12/07/07

Plan Sheet / Specification Reference= Plan Sheet #466-468

Question= In the sewer line encasement data box under remarks, a reference is made to see "SSD-11", where is this sheet and what does it show?

  • Per the Design Sequencing nature of this project, the Details will be provided post award and approval of the project.


33

Q:12/06/07
R:12/07/07

Plan Sheet / Specification Reference= Plan Sheet #514-515

Question= Plan indicates a "Sleeve Encase in Concrete See Detail". Is this per detail sheet 520, and how is this item paid?

  • Yes and it is paid for by item # 148 "510 MM CEMENT MORTAR LINED AND COATED WATER MAIN.



34

Q:12/06/07
R:12/11/07

Plan Sheet / Specification Reference= Bid Item #143

Question= What does this item pay for?

  • Please bid per the current contract documents.


35

Q:12/06/07
R:12/10/07

Plan Sheet / Specification Reference= bid items 233,237,244,248

Question= Are there any plans or specifications that describes this work?

  • Yes, please refer to section 10-3.02 "COST BREAK-DOWN" of the Special Provisions. The plans will be provided as part of the deliverables.


36

Q:12/06/07
R:12/07/07

Plan Sheet / Specification Reference= 10-1.44 Asphalt Concrete, page 266

Question= Item 10-1.44 Asphalt Concrete, General, says "The asphalt concrete shall be treated with liquid anti-strip in conformance with Liquid Anti-Strip Treatment of Asphalt Concrete of these special provision". Where can I find the Liquid Anti-Strip Treatment of Asphalt Concrete of the special provision? Is there any specific dosage required for anti-strip? Is there any TSR requirement? If yes, what is the TSR value (i.e. 70)?

  • The Liquid Anti-Strip Treatment of Asphalt Concrete does not apply to this project.

    Is this a QC/QA Project?
  • No.


37

Q:12/06/07
R:12/07/07
  • Plan Sheet / Specification Reference=

    Question= Are there any soil borings on the EF1 ("Enrico Fermi") Select Materials Site? If so, how do I get them?
  • Please refer to the "DILLARD'S PROPERTY INFORMATION" link, above.

 


38

Q:12/07/07
R:12/11/07

Plan Sheet / Specification Reference= Bid item #144 - 1500 MM Welded Steed Pipe Casing (10MM).  Plan sheet 474 of 895.

Question= The Table of Sewer Quantities on plan sheet 474 shows 193.4 m of 1500 MM Steel Casing.  We do not find any 1500 MM Casing on the Sewer plans sheets 465 thru 472.  Where is this casing located and at what depth?

  • Please bid per the current contract documents.


39

Q:12/07/07
R:12/12/07

Plan Sheet / Specification Reference= Item 107 & 109  Furnish Sign Structure, Sheets 659-667 of 895

Question= It appears you are missing multiple sheets for the overhead sign structures.  There should be 11 Truss structures and 9 Lightweight Structures per the summary on sheets 666-667 and per the weight on the bid schedule yet we only have drawings for 8 truss structures and 2 lightweight structures.  Also the pages we do have for the bridge truss structures are incomplete.  They do not give post types, post heights, sign placement etc... which is necessary for bidding (sign 17 bridge truss does give this info. but the rest do not).

  • Please bid per the current contract documents.


40

Q:12/07/07
R:12/10/07
Plan Sheet / Specification Reference= #85, 401000, Concrete Pavement

Question= Per section 10-1.45 Jointed Plain Concrete Pavement, under Dowel Placement, it is stated that "Dowel bars shall be placed as shown on the plans by using dowel bar baskets".  Will mechanical insertion of dowels be allowed?
  • The replacement of mechanically inserted dowels for dowel bar baskets will not be allowed.

41

Q:12/07/07
R:12/10/07

Plan Sheet / Specification Reference=

Question= Traffic control chart no 6 allows the use of the detour for Britannia for 120 calender days.  This is not enough time to construct the bridge and all its appertances.  Please allow this chart to be used for 360 days.

  • Please bid per the current contract documents.


42

Q:12/07/07
R:12/10/07
Plan Sheet / Specification Reference=

Question= The general plan for La Media shows a min vertical clearance of 5 meters.  The required falsework opening requires a span of 15.9 meters plus a pedestrian opening of 1.52 meters.  The required vertical clearance is 4.6 meters.  These requirements makes a falsework span of approx 17.4 meters plus 8 feet for clearances this requires a 65 foot span and the available vertical distance is .4 meters. Please correct these the plans and specifications to allow the construction of this bridge.
  • Please bid per the current contract documents.

 


43

Q:12/10/07
R:12/12/07

Plan Sheet / Specification Reference= Item #182 :  Concrete (Apron & Ditch Lining)
Plan Sheet #280
Spec Section: 10-1.67

Question= Drainage Quantity Sheet DQ-32 (Ref:  DS E-2 unit : 'g') denotes a large quantity of Concrete Ditch Lining that has no detail given.  The plan, nor the profile call out for unit 'g' on DS E-2.  There is a ditch shown at the end of the RCB, however, it is shown as 'Rock Mulch' on compacted soil (not concrete) and detailed on sheet DD-16.

Please clarify ...

  • Please bid per the current contract documents.

44

Q:12/11/07
R:12/11/07

Plan Sheet / Specification Reference= Bid Item #144

Question= What does this item pay for?

  • Please bid per the current contract documents.

45

Q:12/11/07
R:12/12/07

Plan Sheet / Specification Reference= Contract No. 11-091824 page 439 CEMENT MOTAR LINED AND COATED STEEL PIPE AND SPECIALS 10-4.03 MATERIALS FOR WATER SYSTEM WORK

Question= 1. What is the coating you want on the steel pipe?
2. What is the governing specification for the welded steel pipe: Otay Water District Specification or the one on page 457?
3. Please review and advise on page 440: "The Contractor shall place 50 mm x 100 mm 18 gage wire mesh reinforcement all around" - It is impossible to have wire mesh for pipes smaller than 30"
4. Please review and advise on page 439:  "The wall thickness tolerances for steel pipe 300 mm diameter and larger shall be governed by the requirements of the ASTM specifications to which the plates or sheets are ordered, but in no case shall the thickness be less than 6.35 mm or as directed by the Engineer.
This contradicts the ASTM specifications (for 6.35mm or 0.25in steel coil we have 0.25 nominal with a ASTM negative tolerance) Can not find steel coils with a min. 6.35 mm, only with a nominal 6.35mm.

  • Please bid per the current contract documents.


46

Q:12/12/07
R:12/12/07
Plan Sheet / Specification Reference= Bid items #143, 144, 145, 146, 147, 148.

Question= We are unable to get an unqualified quote from any CMLC supplier that would guarantee to provide 100% "domestic Buy America" steel in the production of their CMLC pipe product. Will CalTrans waive the "Buy America" requirement for this particular material?

  • No.