BIDDER'S INQUIRIES & RESPONSES
DISTRICT 11 CONSTRUCTION

 
CONTRACT NO: 11-256504
ROUTE / KP 11-SD-188-0.0/0.4 
LOCATION In San Diego County At Tecate From The Mexico Border To 0.2 Km North Of Thing Road..
DESCRIPTION Construct Commercial Vehicle Enforcement Facility (cvef).
ESTIMATE $ 14,500,000
ADVERTISE DATE 08/14/2006
BID OPENING 09/28/2006
FINAL  POSTING 09/27/06    @   15:20

BID RESULTS

1
Erreca's Inc. $14,417,974.00

The Caltrans District 11 Office is located at 2829 Juan Street, San Diego, CA 92110. The mailing address is P.O. Box 85406, San Diego, CA 92186-5406. The District 11 Duty Senior telephone number is (619) 688-6635. Please submit all inquiries in the proper format by fax to (619) 688-6988 or e-mail to:
Duty_Senior_Const_District11@dot.ca.gov.
The responses to bidder' inquiries, unless incorporated into a formal addenda to the contract, are not a part of the contract and are provided for the bidder's convenience only. In some instances, the question and answer may represent a summary of the matters discussed rather than a word-for-word recitation. The responses may be considered along with all other information furnished to prospective bidders for the purpose of bidding on the project. The availability or use of information provided in the responses to bidder' inquiries is not to be construed in any way as a waiver of the provisions of Section 2-1.03 of the Standard Specifications or any other provision of the contract, the plans, Standard Specifications or Special Provisions, nor to excuse the contractor from full compliance with those contract requirements. Bidders are cautioned that subsequent responses or contract addenda may affect or vary a response previously given.
Caltrans District 11 Construction Department has developed this method of answering Bidder's Inquiries to better serve the needs of the Contractors who bid on our Projects. Caltrans District 11 Construction Department will post all of the questions submitted by any of the contractors that are registered Planholders for that Contract, but reserves the right to not answer any questions deemed unsatisfactory for public viewing.
The BIDDER'S INQUIRIES & RESPONSES will be updated continuously and all attempts will be made to do the final posting by 15:00 on Wednesday prior to the bid opening.
INFORMATION AVAILABLE
 
CROSS SECTIONS
BID ITEMS
 SPECIALS
PLANS
 PLANHOLDERS
 



ADDENDUM
 


 


 
 

BIDDER'S INQUIRY SUBMITTAL FORM
 


 

Inquiry No.
Inquiry
         1
    Q:08/16/06
    R:09/13/06
Plan Sheet / Specification Reference=Plans
 

Question=Are there cross sections available for this project? If so when and where can I obtain them?
 
 
 

  • Cross sections are available as of 9/13/06 and can be downloaded for printing from the link above at any local printing firm or on your own printing equipment: 
     MESA BLUEPRINT 
     5560 Ruffin Road Suite 5 
     San Diego, CA 92123 
     (858) 541-1500    FAX (858) 278-0558 
     e-mail to  plot@mesablueprint.com San Diego, CA 92123 

             2
    Q:08/29/06
    R:09/05/06
Plan Sheet / Specification Reference=84 Minor Concrete Misc. Construction, plan sheets 26, 93

29 Remove Underground Storage Tank, Section 10-1.30 page 197 
 

Question=84  Please provide details for the construction of "Retaining Concrete Block" 

  •       Constructions Details Sheet C-12 "RETAINING CONCRETE BLOCK DETAIL"


29  What is the size of this tank (l-w-d, or gallons), where is the location, and what do expect it to contain? 
 

  •  600 gal.
  •  Sheet L-3 "REMOVE UNDERGROUNG STORAGE TANK" about 20 m Rt. of S-line Sta. 12+60.  Sta. 12+85 
  •  The tank is empty. 


 

            3
    Q:09/05/06
    R:0x/xx/06

Plan Sheet / Specification Reference= Sheet PD-3, Summary sheet # PDQ-1
 

Question=It appears that blue thermoplastic is called out for the ADA access "paths of travel"... Typically "raised profiles" materials are not used where disabled persons traverse to gain access to various facilities... Additionally Blue thermoplastic is not a readily available material... Please clarify!! 
 

  • Per Section 4-1.03 "Changes," of the Standard Specifications a CCO will be issue to eliminate  blue thermoplastic and to place  blue paint. 


Also please review the use of " Temp. Stripe Tape" where heavy trucks turn and travel. By experience, this material will not hold up under these conditons...
 

  • Please bid per the contract documents.
 
    4
    Q:09/05/06
    R:09/06/06

Plan Sheet / Specification Reference=35  Roadway Excavation 
 

Question=In the Material Handout, Foundation Recommendation section, page 9 states..."all the boring locations and data are shown on the Log of Test Boring sheets..."

Where can we obtain this information? 
 

  • Sheet ST-50 "LOG OF TEST BORINGS 1 OF 10,"
 
     5
    Q:09/12/06
    R:09/26/06
 
Plan Sheet / Specification Reference=Un-scheduled Light fixture
Sheet EE6-3

Question=Please schedule fixture type F3 shown in the Carbon Filter Room.
 

  • Please bid the project per the current contract documents.


 

 
 
 

            6 

    Q:09/13/06
    R:09/20/06
Plan Sheet / Specification Reference=Sections 12-16.06 & 12-16.07

Question=Could a list of 3 Manufacturers and or Vendors be provided for the systems and items listed in Section 12-16.06 Vehicle Monitoring & Signal System and Section 12-16.07 Truck Weighing Electrical System?
 

  • Caltrans does not keep lists of manufactures or vendors.
 
              7
    Q:09/25/06
    R:09/26 /06
 
Plan Sheet / Specification Reference=Sheet W-1. New "D" line shown parallel to sewer line.

Question=Sheet W-1 shows an new equipment drain line from the GAC filter to what appears to be a manhole. Detail sheetd SS-1 and SS-2 show only a single sewer drain line coming from The GAC filter. 

1)Which is correct?

2)If a seperate equipment drain line is required, please clarify what it is connected to.
 

  • Please bid the project per the current contract documents.
 
 

           8

    Q:09/25/06
    R:09/27/06
 

Plan Sheet / Specification Reference=Specification Page 516 paragraph 12-16.09 Standby Generator. 
 

Question=Section 12-16.09 pp. Products, calls out the generator to be a 4 cycle LPG fuel type...

It then describes Liquid Petroleum Gas (LPG) fuel. Or Gasoline. The fuel tank for the generator is Liquid Propane Gas. 

Is the generator to be dual fuel; gas and propane? 
 

  • Please bid per the current contract documentsls
.
 
 
             9
    Q:09/25/06
    R:09/26 /06
 

Plan Sheet / Specification Reference=62-64, Furnish Signs, SQ-4,5, Furnish Signs
 

Question=The Furnished Roadside Sign Panel chart has incorrect ASTM Retro Reflective Types listed with respect to the BACKGROUND AND LEGEND. For example, Sign 140 R1-1 cannot have Type VII BACKGROUND and Type VIII LEGEND. Also, for most of the Regulartory and Warning signs they need to have the same ASTM Type Sheeting, either III or IV;not both. Some guide signs have a combination of both.
 

  • Thank you, Caltrans will look into.

 
 
 

            10

    Q:09/25/06
    R:09/27 /06
 
Plan Sheet / Specification Reference=Detail 5/ST-42 107mm wide trench drain.
 

Question=The trench drain shown in detail 5 directs us to the Architectural plans for the Trench Grate Details. Inspection Bay Floor Plan does not show the trench drain. Mechanical sheet M-5 shows trench drains for the at grade areas and shows an Inspection Pit Drain but nothing else. 
What is the extent of the trench drain in the Inspection Bay Pit?
 

  • See Detail A,"INSPECTION PIT SECTION," on sheet A-27 and Detail 1&4 on sheet A-28.

 
 
 

            11

    Q:09/25/06
    R:09/26 /06
 
 

Plan Sheet / Specification Reference=Spec Section 90-6.03, para 7, requiring
concrete to be delivered and placed within 1.5 hours as it pertains to bid
items 84 & 85, minor concrete.
Also, Detail for Retaining Concrete Block per C - 12
 
 

Question=Minor concrete items are scheduled to be installed in multiple
stages, some of small quantities.  Concrete will probably be
purchased/delivered from source that will require considerable delivery
time.  Will Caltrans allow any addition of admixtures to extend the 1.5 hour
delivery & place time, and if so, what admixtures are acceptable?
 

  • Please bid the project per the current contract documents.


Detail for Retaining Concrete Block, sheet C - 12, indicates a variable
height (0.3 - 1.2) and variable depth of embeddment into ground (0.3 - 0.8).
The quantity shown on qty sheets would indicate it is all H = 1.2.  Where is
information indicating height of wall & depth of embeddment at each
location?

  •  Height as required per field conditions ( 0.3-1.2)

No rebar is indicated, will any rebar be required?
 

  • Plans do not indicate to use rebar

 
 
 